Faults
Fault 338: 2015-2016’s ONLY - Blown Fuse Panel 3: F6 (1.5 amp)
Causes
Troubleshooting
Fixes
• Faulty PLC.
• Test for ground short.
• Replace PLC.
• Faulty wiring.
• Inspect entire wiring path
checking for continuity, ground,
and proper voltage.
• Repair/Replace faulty wiring
section.
Fault 339: 2015-2016’s ONLY - Blown Fuse Panel 3: F7 (2 amp)
Causes
Troubleshooting
Fixes
• Faulty analog sensor.
• See Test 19.
• Replace analog sensor.
• Faulty wiring.
• Inspect entire wiring path
checking for continuity, ground,
and proper voltage.
• Repair/Replace faulty wiring
section.
Fault 340: 2015-2016’s ONLY - Blown Fuse Panel 3: F8 (2 amp)
Causes
Troubleshooting
Fixes
• Faulty PLC in/output card.
• Test for ground short.
• Replace PLC in/output card.
• Faulty wiring.
• Inspect entire wiring path
checking for continuity, ground,
and proper voltage.
• Repair/Replace faulty wiring
section.
Fault 341: 2015-2016’s ONLY - Blown Fuse Panel 3: F9 (2 amp)
Causes
Troubleshooting
Fixes
• Faulty PLC ethernet switch.
• Test for ground short.
• Replace PLC ethernet switch.
• Faulty wiring.
• Inspect entire wiring path
checking for continuity, ground,
and proper voltage.
• Repair/Replace faulty wiring
section.
Fault 342: 2015-2016’s ONLY - Blown Fuse Panel 3: F10 (1.5 amp)
Causes
Troubleshooting
Fixes
• Faulty touch screen.
• Test for ground short.
• Replace touch screen.
• Faulty wiring.
• Inspect entire wiring path
checking for continuity, ground,
and proper voltage.
• Repair/Replace faulty wiring
section.