Product Manual Type:
637f
07-02-10-01-E-V0304.doc
Diagnosis and trouble shooting
9.2
Reset of a regulator trouble
A general precondition for correct execution of the Reset is the elimination of the error cause.
The error signals
at
blinking
(BIAS)
of the drive can be reset via:
1. Control voltage OFF/ON
,
2. the serial command “Drive Reset“ 0x02
The host login must be occurred.
The drive must be deactivated via the serial command “deactivate Drive“ 0x00.
3. the fieldbus-command “ Drive Reset“ 0x16 (22 decimal)
The host login must be occurred via the BUS command 0x01.The drive must be deactivated
via the BUS command “deactivate Drive“ 0x14.
The fieldbus command “Drive Reset“ with constant repetition of the fieldbus command 0x16 will be
works-off only once.
For further processing, it is necessary, meanwhile to send another control word
(e.g. 0 status order).
4. a 0 – 1 flank on input X10.11
Precondition:
- The input X10.11 is with function 1“Reset drive fault“ configured
(EASYRIDER
®
Windows – Software)
-
There is no host login.
-
The input Active,(X10.22) is inactive (0V)
1)
-
The signal must be present min. 250 ms
Notice !!
After remove of the tracking error deactivation the warning message
(tracking error) is active up to the next move command.
The
error signal
(releasing before ready) can be reset by deactivation the drive.
1)
Hint:
With the assembly of the option module SBT you kindly note the extended functions of the
signals (see documentation 07-02-10-02-E..)