6-86
Programming Your Application
590+ Series DC Digital Converter
SYSTEM PORT P3
Use this block to configure the drive's RS232
programming port (P3).
Refer to Chapter 14: “Serial Communications” -
System Port P3 for further information.
The block is viewed in three menus on the MMI:
SYSTEM PORT P3, P3 SETUP and BISYNCH SUPPORT.
SYSTEM PORT P3
This MMI menu contains parameters for transferring data to and from a PC. Refer to Chapter
14.
P3 SETUP
This MMI menu contains the communication set-up parameters for System Port P3. Refer to
page 6-87 and Chapter 14 for information on the 5703 SUPPORT sub-menu.
BISYNCH SUPPORT
This MMI menu contains parameters for supporting the BISYNCH protocol.
The P3 port is a non-isolated serial communications port built in to the drive's Control Board.
It is used off-line (while the drive is stopped) for transferring and saving drive configuration
files using a personal computer (PC) running a serial communications program, or on-line
(while the drive is running) when using the SSD Drives 5703 Setpoint Repeater Unit.
You can also use the P3 port to transfer configuration files by connecting to a PC running the
Windows
TM
compatible software package "ConfigEd Lite". Refer to the ConfigEd Lite
manual RG352747.
MMI Menu Map
1
SERIAL LINKS
2
SYSTEM PORT P3
DUMP MMI (TX)
UDP XFER (RX)
UDP XFER (TX)
VERSION NUMBER
System Port P3
0x00C0
–
[332] ERROR REPORT
CELite (EIASCII)
–
[130] MODE
0x0000
–
[329] GROUP ID
0x0000
–
[330] UNIT ID
MMI Menu Map
1
SERIAL LINKS
2
SYSTEM PORT (P3)
3
P3 SETUP
MODE
5703 SUPPORT
P3 BAUD RATE
MMI Menu Map
1
SERIAL LINKS
2
SYSTEM PORT (P3)
3
P3 SETUP
4
BISYNCH SUPPORT
GROUP ID (GID)
UNIT ID (UID)
ERROR REPORT
Parameter
Tag
Range
ERROR REPORT
332
0x0000 to 0xFFFF
Displays the last error as a hexadecimal code. Writing any value to this parameter will set
the value to >00C0 (No Error). Refer to Chapter 14: “Serial Communications” - Reference
for a list of codes.
MODE
130
See below
Determines the function of the 5703 unit if present. Four options are available:
0 : DISABLED
1 : 5703 MASTER
2 : 5703 SLAVE
3 : CELite (EIASCII)
P3 BAUD RATE
198
See below
Transmission rate. Four options are available:
0 : 300
1 : 600
2 : 1200
3 : 2400
4 : 4800
5 : 9600 (default)
6 : 19200
GROUP ID
329
0x0000 to 0x0007
(GROUP ID (GID))
The SSD Drives protocol group identity address.
UNIT ID
330
0x0000 to 0x000F
(UNIT ID (UID))
The SSD Drives protocol unit identity address.
VERSION NUMBER
155
0x0000 to 0x000F
The drive's version number as seen over the System Port (P3).
Serial communications mnemonic = V0. The version number cannot be changed, and is
software version dependent.