Programming Your Application
6-5
590+ Series DC Digital Converter
ANALOG INPUTS
The analog input block is used to scale and clamp the inputs for terminals A2 to A6.
Note:
Terminal ANIN 2 (A3) is p
permanently
connected to SETPOINT 2 (A3) in the SPEED
LOOP function block and to the Current
Demand via I DEMAND ISOLATE (the current demand isolate switch) in the CURRENT
LOOP function block.
To avoid interference with other drive functions when not required: the parameter
RATIO 2 (A3) (Tag 7 in the SPEED LOOP function block) must be set to zero; and the I
DMD. ISOLATE parameter (Tag 119 in the CURRENT LOOP function block) must be set
to DISABLED, i.e. selecting the Speed Loop as shown in the Main Block Diagram.
Because ANIN 2 (A3) is scanned synchronously with the current loop (typically every
3.3/2.6ms, 50/60Hz), it should be used for any signal whose response is critical e.g. a
trim input from an external positioning system or load share.
Analog Input 2
OUTPUT [493]
–
0.00 %
1.0000
–
[233]
CALIBRATION
100.00 %
–
[234]
MAX VALUE
-100.00 %
–
[235]
MIN VALUE
ANIN 1 (A3)
[ 51]
–
0.00
VOLTS
Analog Input 1
OUTPUT [246]
–
100
1.0000
–
[230]
CALIBRATION
100.00 %
–
[231]
MAX VALUE
-100.00 %
–
[232]
MIN VALUE
ANIN 1 (A2)
[ 50]
–
0.00
VOLTS
Analog Input 3
OUTPUT [249]
–
5
1.0000
–
[236]
CALIBRATION
100.00 %
–
[237]
MAX VALUE
-100.00 %
–
[238]
MIN VALUE
ANIN 3 (A4)
[ 52]
–
0.00
VOLTS
MMI Menu Map
1
SYSTEM
2
CONFIGURE I/O
3
ANALOG INPUTS
4
ANIN 1 (A2)
4
ANIN 2 (A3)
4
ANIN 3 (A4)
4
ANIN 4 (A5)
4
ANIN 5 (A6)
CALIBRATION
DESTINATION TAG
MIN VALUE
MAX VALUE
Analog Input 4
OUTPUT [250]
–
48
1.0000
–
[239]
CALIBRATION
200.00 %
–
[240]
MAX VALUE
-200.00 %
–
[241]
MIN VALUE
ANIN 4 (A5)
[ 53]
–
0.00
VOLTS
Analog Input 5
OUTPUT [247]
–
301
1.0000
–
[242]
CALIBRATION
200.00 %
–
[243]
MAX VALUE
-200.00 %
–
[244]
MIN VALUE
ANIN 5 (A6)
[ 54]
–
0.00
VOLTS
Parameter
Tag
Range
OUTPUT
246, 249, 250, 247
0 to 639
(DESTINATION TAG)
The destination Tag No. of the scaled analog input value. Refer to “Special Links”, page 6-1.
OUTPUT
493
.xx %
This parameter is the output diagnostic for terminal A3 (ANIN 2). Note by default 10V =
100%. To obtain a different range, adjust the CALIBRATION, MAX VALUE and MIN
VALUE parameters. Use this parameter to access the calibrated value of ANIN 2 (via an
internal link for example).
CALIBRATION
230, 233, 236, 239, 242
-3.0000 to 3.0000
The analog input scaling ratio. For a value of 1.0, 10V = 100%.
MAX VALUE
231, 234, 237, 240, 243
-300.00 to 300.00 %
The maximum value of the scaled analog input.
MIN VALUE
232, 235, 238, 241, 244
-300.00 to 300.00 %
The minimum value of the scaled analog input.
ANIN 1 (A2) to ANIN 5 (A6)
50, 51, 52, 53, 54
xxx.xx VOLTS
Refer to the DIAGNOSTICS function block description, page 6-23.