5-8
The Operator Station
590+ Series DC Digital Converter
Menu Shortcuts and Special Key Combinations
Quick Tag Information
Hold down the
M
key for approximately ½ second in any Menu System parameter to display the
Tag number for that parameter.
RAMP ACCEL TIME
10.0 SECS
RAMP ACCEL TIME
TAG NO = 2
M
HOLD
Changing the Stack Size (3-button reset)
Note:
This is only necessary if you are installing a new control board on an existing stack.
Power-up the drive holding three keys as described below.
Caution
At this point, the 590+ thinks that it is a 34A model. It is vitally important that it is
configured for the correct power rating or irreparable damage may occur to the drive
when it attempts to run the motor.
Continue to select the correct Product Code rating. Perform a PARAMETER SAVE now (refer
to Saving Your Application, page 5-13).
Hold down the keys opposite:
Power-up the drive, continue
to hold for at least 2 seconds
M TO SET PCODE
E TO SAVE PCODE
E TO SAVE PCODE
PRODUCT CODE
PRODUCT CODE
DC 4Q 15A
PRODUCT CODE
DC 2Q 15A
E TO SAVE PCODE
PRODUCT CODE
M TO SET PCODE
E TO SAVE PCODE
DIGITAL DC DRIVE
DC 2Q 15A
▲
▼
E
PROG
M
M
▲
E
E
E
HOLD