6-8
Programming Your Application
590+ Series DC Digital Converter
AUX I/O
The auxiliary I/O parameters are primarily
intended to extend the functionality of the
serial links by allowing them access to the
drive analog and digital terminals.
START, JOG and ENABLE from digital input
terminals C3, C4 and C5 respectively connect
directly to the AUX I/O block. Output signals
are then sent to the drive start and drive enable
logic and the JOG/SLACK function block.
Aux I/O
START (C3)
[ 68]
–
OFF
DIGIN (C4)
[ 69]
–
OFF
DIGIN (C5)
[ 70]
–
OFF
SEQ STATUS
[537]
–
0x0000
REM SEQUENCE
[536]
–
0x0000
ON
–
[161] AUX START
ON
–
[227] AUX JOG
ON
–
[168] AUX ENABLE
OFF
–
[ 94] AUX DIGOUT 1
OFF
–
[ 95] AUX DIGOUT 2
OFF
–
[ 96] AUX DIGOUT 3
0.00 %
–
[128] ANOUT 1
0.00 %
–
[129] ANOUT 2
OFF
–
[496] JOG/SLACK
OFF
–
[497] ENABLE CURRENT
FALSE
–
[535] REM. SEQ. ENABLE
MMI Menu Map
1
SETUP PARAMETERS
2
AUX I/O
AUX START
AUX JOG
ENABLE
AUX DIGOUT 1
AUX DIGOUT 2
AUX DIGOUT 3
ANOUT 1
ANOUT 2
JOG/SLACK
AUX ENABLE
REM.SEQUENCE
REM.SEQ.ENABLE
SEQ STATUS
Parameter
Tag
Range
START (C3)
68
OFF / ON
Refer to the DIAGNOSTICS function block description, page 6-23.
DIGIN (C4)
69
OFF / ON
Refer to the DIAGNOSTICS function block description, page 6-23.
DIGIN (C5)
70
OFF / ON
Refer to the DIAGNOSTICS function block description, page 6-23.
SEQ STATUS
537
0x0000 to 0xFFFF
An input data word that reports the status of the important system flags that can be read over a
filed bus. (Refer to “Remote Sequencing Command” below).
REM. SEQUENCE
536
0x0000 to 0xFFFF
(REM.SEQUENCE)
A control word that allows the device to be operated remotely over a field bus.
REM. SEQ. ENABLE must be TRUE to enable this function. (Refer to “Remote Sequencing
Command” below).
AUX START
161
OFF / ON
Software Start/Run command. Auxiliary Start is ANDed with the Start input , C3, to generate
Drive Start. This should normally be left ON.
AUX JOG
227
OFF / ON
Software Jog command. Auxiliary Jog is ANDed with the Jog input , Tag 496 (by default
C4), to generate Drive Jog. This should normally be left ON.
AUX ENABLE
168
OFF / ON
Software Enable command. Auxiliary Enable is ANDed with the Enable input , Tag 497 (by
default C5), to generate Drive Enable. This should normally be left ON.