The Operator Station
5-9
590+ Series DC Digital Converter
This is the preferred way of selecting a new product code. The available product codes are
restricted to the set of codes that match the stack that the control board is fitted to.
If the product code is changed during the 3-button reset, the following parameters are set to their
default value for the new product code:
Tag 523
ARMATURE CURRENT
Tag 524
FIELD CURRENT
Tag 201
REGEN MODE
Note:
The 3-button reset does not cause the default configuration to be loaded.
Resetting to Factory Defaults (2-button reset)
Power-up the drive holding two keys as described below.
The drive is now safely configured with the default settings detailed in this manual for the
existing product code.
The default configuration is not automatically saved to non-volatile memory, so you must
perform a PARAMETER SAVE (refer to Saving Your Application, page 5-13).
Hold down the keys opposite:
Power-up the drive, continue to
hold for at least 2 seconds
INITIALIZING
FACTORY DEFAULTS
DIGITAL DC DRIVE
DC 2Q 15A
▼
▲
HOLD