Page 86 of 87
Property Identifier
Writable
Required
Optional
Property Data
Object_Identifier
Yes
X
DEVICE #
Object_Name
Yes
X
"SonNet-‐BACnet-‐Gateway"
Object_Type
No
X
DEVICE
System_Status
No
X
Operational
Vendor_Name
No
X
"Sontay Limited"
Vendor_Identifier
No
X
662
Model_Name
No
X
"SBIP"
Firmware_Revision
No
X
"0.9.1"
Application_Software_ Version
No
X
"1.2.5"
Location
Yes
X
"Building 1"
Description
Yes
X
"SonNet devices"
Protocol_Version
No
X
1
Protocol_Revision
No
X
12
Protocol_Services_ Supported
No
X
stack library filled
Protocol_Object_Types_ Supported
No
X
stack library filled
Object_List
No
X
stack library filled
Max_APDU_Length_ Accepted
No
X
1476 bytes
Segmentation_Supported
No
X
None
APDU_Timeout
No
X
3000ms
Number_Of_APDU_Retries
No
X
3
Device_Address_Binding
No
X
{}
Database_Revision
No
X
counter
Data Link Layer Options
X
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-‐3, Ethernet (Clause 7)