Page 64 of 87
Description of BACnet Points by Device
The RF-‐RXS-‐B Receiver
RF-‐RXS-‐B Receiver
Point
BACnet Point Type
R/W
Notes
Online Status
Binary Input
R
The online status of the receiver on the wireless network
End Device without CO
2
Functionality
ED without CO
2
Functionality
Item
Point
BACnet Point Type
R/W
Notes
1
Temperature
Analogue Input
R
Temperature Value (if fitted)
2
Humidity
Analogue Input
R
RH Value (if fitted)
3
Setpoint
Analogue Input
R
Setpoint Value (if fitted)
4
VFC Count
Analogue Value
RW
How many input closures the VFC has had (if fitted)
5
Parent LQI
Analogue Value
R
The link quality index between the device and its parent
6
Sensor Measurement Interval
Analogue Value
RW
How often the device wakes to send measurement values
7
Momentary Switch
Binary Input
R
Momentary Switch Status (if fitted)
8
VFC Input
Binary Input
R
VFC Input Status (if fitted)
9
VFC Count Reset
Binary Input
RW
Reset the VFC count
10
Low Battery
Binary Value
R
Alarm status -‐ True if the battery voltage falls below 3.3Vdc
11
Online Status
Binary Value
R
The online status of the ED on the wireless network
12
Sensor Fault
Binary Value
R
Status of the sensing element(s)
13
Fan Speed Switch
Multi-‐State Input
R
Fan Speed Switch Value (if fitted)
End Device with CO
2
Functionality
ED with CO
2
Functionality
Item
Point
BACnet Point Type
R/W
Notes
1
Temperature
Analogue Input
R
Temperature Value (if fitted)
2
CO
2
Analogue Input
R
CO
2
Value
3
Humidity
Analogue Input
R
RH Value (if fitted)
4
VFC Count
Analogue Value
RW
How many input closures the VFC has had (if fitted)
5
Parent LQI
Analogue Value
R
The link quality index between the device and its parent
6
VFC Input
Binary Input
R
VFC Input Status (if fitted)
7
VFC Count Reset
Binary Input
RW
Reset the VFC count
8
CO
2
Auto Calibration
Binary Input
RW
Enable of disable CO
2
ABC
9
Low Battery
Binary Value
R
Alarm status -‐ True if the battery voltage falls below 3.3Vdc
10
Online Status
Binary Value
R
The online status of the ED on the wireless network
11
Sensor Fault
Binary Value
R
Status of the sensing element(s)
Router without CO
2
Functionality
Router without CO
2
Functionality
Item
Point
BACnet Point Type
R/W
Notes
1
Temperature
Analogue Input
R
Temperature Value (if fitted)
2
Humidity
Analogue Input
R
RH Value (if fitted)
3
Setpoint
Analogue Input
R
Setpoint Value (if fitted)
4
VFC Count
Analogue Value
RW
How many input closures the VFC has had (if fitted)
5
Parent LQI
Analogue Value
R
How often the device sends measurement values
6
Momentary Switch
Binary Input
R
Momentary Switch Status (if fitted)
7
VFC Input
Binary Input
R
VFC Input Status (if fitted)
8
VFC Count Reset
Binary Input
RW
Reset the VFC count
9
PIR
Binary Input
R
PIR Status (if fitted)
10
Online Status
Binary Value
R
The online status of the router on the wireless network
11
Sensor Fault
Binary Value
R
Status of the sensing element(s)
12
Fan Speed Switch
Multi-‐State Input
R
Fan Speed Switch Value (if fitted)