![Sontay RF--RXS--B User Manual Download Page 69](http://html1.mh-extra.com/html/sontay/rf-rxs-b/rf-rxs-b_user-manual_1322792069.webp)
Page 67 of 87
Standard Device Binding Methods Supported
The table below lists all the standard Device Binding methods supported by this device.
Send Who-‐Is, receive I-‐Am (BIBB DM-‐DDB-‐A)
X
Receive Who-‐Is, send I-‐Am (BIBB DM-‐DDB-‐B)
Send Who-‐Has, receive I-‐Have (BIBB DM-‐DOB-‐A)
X
Receive Who-‐Has, send I-‐Have (BIBB DM-‐DOB-‐B)
Manual configuration of recipient device's network number and MAC address
None of the above
Standard Object Types Supported
The following is a list of the standard object types, as defined by ASHRAE, that are currently supported by
this product. This section includes object type details.
Analog Input Object Type
Dynamically creatable using BACnet's CreateObject service?
No
Dynamically deletable using BACnet's DeleteObject service?
No
Property Identifier
Writable
Required
Optional
Property Data
Object_Identifier
No
X
ANALOG INPUT #
Object_Name
Yes
X
"Temperature"
Object_Type
No
X
ANALOG INPUT
Present_Value
No
X
Temperature in Degrees Celsius
Status_Flags
No
X
{FALSE,FALSE,FALSE,FALSE}
Event_State
No
X
{NORMAL}
Out_Of_Service
No
X
FALSE
Units
No
X
Degrees Celsius
Reliability
No
X
no-‐fault-‐detected
Property Identifier
Writable
Required
Optional
Property Data
Object_Identifier
No
X
ANALOG INPUT #
Object_Name
Yes
X
"Humidity"