Page 80 of 87
Status_Flags
No
X
{FALSE,FALSE,FALSE,FALSE}
Event_State
No
X
{NORMAL}
Out_Of_Service
No
X
FALSE
Polarity
No
X
Normal Polarity
Reliability
No
X
no-‐fault-‐detected
Binary Value Object Type
Dynamically creatable using BACnet's CreateObject service?
No
Dynamically deletable using BACnet's DeleteObject service?
No
Property Identifier
Writable
Required
Optional
Property Data
Object_Identifier
No
X
BINARY VALUE #
Object_Name
Yes
X
"Low Battery"
Object_Type
No
X
BINARY VALUE
Present_Value
No
X
Active=Low Battery, or Inactive=Battery
Okay
Status_Flags
No
X
{FALSE,FALSE,FALSE,FALSE}
Event_State
No
X
{NORMAL}
Out_Of_Service
No
X
FALSE
Polarity
No
X
Normal Polarity
Reliability
No
X
no-‐fault-‐detected
Property Identifier
Writable
Required
Optional
Property Data
Object_Identifier
No
X
BINARY VALUE #
Object_Name
Yes
X
"Online Status"
Object_Type
No
X
BINARY VALUE
Present_Value
No
X
Active=Online, or Inactive=Offline
Status_Flags
No
X
{FALSE,FALSE,FALSE,FALSE}
Event_State
No
X
{NORMAL}
Out_Of_Service
No
X
FALSE