Page 11 of 87
The RF-‐RXS-‐B BACnet IP System Receiver
The SonNet
®
RF-‐RXS-‐B receiver collects data from all other devices on the radio network, including
measurements from sensors, link quality for all links formed in the network, battery levels for all battery
powered devices, hours run for all devices and the current status of all devices.
NB
Each receiver can
support a maximum of 16 “children”, which can consist of a maximum of 12 battery powered nodes and 4
routers,
or
up to 16 routers
if
there are no battery powered nodes.
•
An RJ45 Ethernet socket is provided for connection to BACnet IP systems.
•
A USB socket is provided for connection to a PC or laptop running the Sontay SonNet CMS
software.
NB
-‐ If the USB port of an
RF-‐RXS-‐B
receiver is connected, the Ethernet port is temporarily disabled until the
USB port is disconnected again.
Receiver Specification
:
Radio Output
2.4 GHz, 16 channels automatically selected
Direct-‐sequence spread spectrum
Compliance
IEEE802.15.4-‐2006
Aerial Characteristics
Gain 3.0dBi
VSWR <2:1
Data encryption
AES 128
Power supply
24Vdc ±15%
24Vac ±15%, 50/60Hz
Communication:
USB 2.0
RJ45 Ethernet (for BACnet IP protocol)
BIBBs supported
DS-‐RP-‐B
DS-‐WP-‐B
DM-‐DDB-‐B
DM-‐DOB-‐B
DM-‐DCC-‐B
DS-‐RPM-‐B
DM-‐RD-‐B
Environmental:
Operating Temp. -‐10 ˚C to +50˚C
Operating RH
0-‐90%, non-‐condensing
Storage Temp
-‐10 to +80˚C
Storage RH
0-‐90%, non-‐condensing
Dimensions
100 x 95 x 65mm
Weight
150g
Country of origin
UK
Refer to product datasheets for installation instructions.