PAT-80
● PAT-85 ● PAT-86 – USER MANUAL
48
NOTE!
During the measurement, the same mains voltage is present at the measuring
socket which powers the tested appliance.
During the measurement of a faulty appliance, RCD switch may be triggered off.
Differential leakage current is measured as a difference between L current and N
current. This measurement takes into account not only current leaking to PE, but al-
so currents leaking to other earthed elements - e.g. water pipe. The disadvantage of
this measurement is the presence of common current (supplied to the tested appli-
ance through L line and returning via N line), which influences the measurement ac-
curacy. If this current is high, the measurement will be less accurate (see
sec. 13
than the measurement of PE leakage current.
The tested appliance must be turned on.
When
Change polarity
is set on
Yes
, after the set time duration is over the tester
automatically changes the polarity of the test mains socket and resumes the test.
As a test result it displays the value of the higher leakage current.
The result of measurement may be affected by the presence of external fields and
by the current used by the appliance.
If the tested appliance is damaged, signaling a 16 A fuse burnout may also mean
that the overcurrent protection device in the mains from which the meter is powered
has tripped.
Summary of Contents for PAT-80
Page 1: ...1...
Page 2: ...2...
Page 97: ...PAT 80 PAT 85 PAT 86 USER MANUAL 95 NOTES...
Page 98: ...PAT 80 PAT 85 PAT 86 USER MANUAL 96 NOTES...
Page 99: ......
Page 100: ......