SOLID AIR ®
CLIMATE SOLUTIONS
•
T +31 598 36 12 21
•
www.solid-air.com
•
32
- 58
Product overview
Technical data
Ordering key
Installations
Accessories
Replacements
Maintenance and operation
The wall is composed of gypsum blocks (minimum density of 995 kg/m³), and with
minimum thickness of 70 mm.
Wall openings dimensions
Damper Ø d [mm]
Applique frame Ø D [mm]
Wall opening [mm]
100
Ø d + 105 mm
Ø d + 115 mm
125-180
Ø d + 95 mm
Ø d + 105 mm
200-315
Ø d + 80 mm
Ø d + 90 mm
1
2
GYPSUM BLOCKS
WALL INSTALLATION
APPLIQUE INSTALLATION FRAME
INSTALLATION
1. Create a wall opening according to the dimensions in the table below.
Damper blade must be closed during installation!
2. Insert fire damper into wall and fasten with screws (8 pcs, 4.8 x 60 mm).
Test the operation of the damper blade!
>
>