The wall is composed of gypsum blocks (minimum density of 995 kg/m³), and with
minimum thickness of 70 mm.
Installatiemateriaal: brandwerende gipspleister of mortel, afgedekt met GKF-gipsplaat.
1
4
2
7
625
625
> 440
625
625
> 440
1
2
3
GYPSUM WALL
INSTALLATION
(MORTEL AFWERKING)
INSTALLATION
1. Create an opening in the wall (minimal dimensions on
). Bend the fixing bracket
(1)
90°. Place the damper in the opening up to the wall limit mark
(7)
on the damper.
Damper blade must be closed during the installation!
2. Fix the damper to the wall using screws (bracket screw hole is 6 mm in diameter).
3. Fill the space between the damper and the wall with mortar
(2)
. Cover the mortar with
GKF gypsum boards
(4)
(12,5 mm thick), and fix them with screws.
*Multiple fire dampers can be installed next to each other or ceiling/wall with the mini-
mal distance of 30 mm between them. See
.
Test the operation of the damper blade!
>
>