INSTALLATION
Electromagnetic operating mechanism, comes with end switches as standard. In case of
fire, the fire damper closes automatically.
Damper closing can be initiated either by thermal fuse melting or remotely by triggering
the electromagnet.
Electromagnet is constantly under power and activates closing of the damper blade in
case the power cuts out. Upon closure, damper blade is locked in closed position and can
only be opened manually. Thermal fuse melting point is 72 °C.
EMS-S mechanism is the same for FDC25/FDC40 fire dampers.
SOLENOID
ACTUATOR EMS-S
TECHNICAL SPECIFICATION
Nominal voltage
Solenoid: 24/48 VDC
Power
Dual voltage Solenoid:
Break of current: P
nom
= 1,6 W
Switching capacity
1 mA...500 mA, 5 VDC...48 VDC
Blade closing time
Spring: 1 second
Blade opening time
Manual
Manual activation
Release button on the casing
Degree of protection
IP 42
Ambient temperature range min. -30 °C, max. 50 °C
Ambient humidity
95 % r.v., non-condensing
Service life
Min. 30,000 cycles
Maintenance
Maintenance-free
Weight
2,5 kg
WIRING DIAGRAM
MAGM
OT
++
--
78
91
0
FC
DC
NF NO
C
NF NO C
1 2
3
4 5
6
MAG
MOT
+
-
+
-
FC = Limit switch - end
DC = Limit switch - start
NO = Normally open
NF = Normally closed
C = Common
MAGM
OT
++
--
78
91
0
FC
DC
NF NO
C
NF NO C
1 2
3
4 5
6
MAG
MOT
+
-
+
-
>
>