MAINTENANCE AND OPERATION
TRANSPORT
After arrival, check the fire damper for transport damage and shortcomings. In case of
any damage or shortcomings, immediately contact your supplier.
STORAGE
If the damper is not installed immediately:
• Remove any wrapping.
• Protect fire damper from dust and contamination.
• Do not expose the fire damper to the effects of weather - store fire damper in dry place.
• Do not store the unit below -20 °C or above 50 °C.
Please properly dispose of packaging material.
MAINTENANCE AND OPERATION
Klimaoprema fire dampers are designed with fully enclosed drive mechanism outside of
the duct and as such do not require cleaning and regular maintenance.
However, activation mechanism should be inspected for proper operation on regular basis.
• Provide at least one annual check of the damper
• After each intervention, provide a systematic cleaning of dust and especially the
solenoid and its movable plate
• Check the if the electrical terminals are tightened.
It is not permitted to alter the dampers in any way nor perform any changes (except for
the service procedures described in this manual) to their structure without the manufac-
turer’s consent.
Provide at least one annual check of the damper. The functional test must be carried out
in compliance with the basic maintenance principles of the European norms EN 13306,
EN 15423 and EN15650.
COMMISSIONING
1. Carefully unpack FDC fire damper - be careful of sharp edges and do not use excessive
force for unpacking.
2. Inspect the fire damper - check the fire damper for damage.
3. Installation of the fire damper - according to the installation instructions (
).
4. Before commissioning: check the fire damper functions.
FUNCTIONS
1. Release mechanism: Damper blade can be closed and opened manually.
2. EMS: Signal testing - the damper blade must close.
3. Electric actuator: Signal testing - the damper blade must close/open.
4. Thermal fuse:
By a button - the damper blade must be closed by pressing the button.
>
>