SOLID AIR ®
CLIMATE SOLUTIONS
•
T +31 598 36 12 21
•
www.solid-air.com
•
6
- 58
Product overview
Technical data
Ordering key
Installations
Accessories
Replacements
Maintenance and operation
TECHNICAL DATA
Fire damper casing is manufactured from galvanized steel sheet, but on demand can be
produced out of:
• Galvanized steel and powder coated
• Stainless steel (AISI 304/316)
• Stainless steel (AISI 304/316) and powder coated
Fire damper for areas with potentially explosive atmospheres are also available.
PRODUCT LABEL
1. Serial number
2. Dimension of the fire damper
3. Type
4. Serial number
5. Production date
6. Mechanism type
7. Classification according to EN 13501-3
8. Declaration of performance
9. Number of the European standard and
year of its publication
10. Barcode
11. CE-mark
Nominal sizes
100 - 800 mm
Casing length
380 mm
Temperature range
-20 °C ... 50 °C
Release temperature
72 °C (standard) of
95 °C (optional with electric actuator)
Volume flow rate range
up to 21.700 m³/h
Differential pressure range
up to 2.000 Pa
Casing air leakage
Class C/ATC3, EN 1751
Closed blade air leakage
Class 2, EN 1751
Upstream velocity
< 12 m/s
EC conformity
EN 13501-3, EN 1366-2, EN 15650, EN 1751,
CPR no. 305/2011
Declaration of performance
DoP 711/2020_12_EN
PRODUCT SPECIFICATIONS
1
3
5
2
4
6
8
9
10
7
Article number:
Size:
Type:
Serial number:
Production date:
Actuator mechanism:
xxxxxxx
d100
FDC25-d100-m230-S4
0000001
14.10.2019
M230
EN15650:2010
Eltt (Ve-Ho) S Cxx
For the fire classification of
this product please consult
declaration of performance.
DOP 711/2017 N
EI 60/90/120 (Ve-Ho i < - > 0) S 500 Pa
This damper should be installed according
to the installation instructions.
For more information: www.solid-air.com
1812 17 1812-CPD-1161