Switching off MyReserve Command
1.
Switch off the AC power supply of the MyReserve
Command (green POWER toggle at the MyReserve
Command 25 bottom plate).
2.
Turn off the inverter by following its shutdown se
-
quence.
3. Turn the DC isolator of MyReserve Command to the
OFF position.
HAZARD
Remember that charged capacitors pose an electrical hazard. A discharge time of 5 minutes
must be observed after shutting down the MyReserve Command before work on the device
can take place.
Important settings on the PV inverter
Additional functions that ensure the optimum operating point of the inverter, even in partially shaded PV systems,
must be deactivated on the inverter. Otherwise, unfavorable voltage levels may occur.
Examples of shadow management functions are
OptiTrac Global Peak or ShadeFix on SMA
devices or
Dynamic Peak
Manager from Fronius.
Follow the instructions in the inverter manufacturer‘s user manual to deactivate these functions.
IMPORTANT
The changing of any Settings on the PV inverter may only be made when the MyReserve is switched OFF.
Non-observance can cause equipment damage.
Disconnect the AC supply on the MyReserve.
The DC cut-off switch on the MyReserve remains switched ON so that the inverter remains awake and setting
changes can be made on the PV inverter.