Pass the cabling through the MyReserve Command protective cover
•
remove seal inserts and synthetic seals from the cable
branch collector disc (included in the accessory kit)
•
pass the AC-, CAN and LAN cable through the collector
disc
•
pass the AC-, CAN- and LAN cable through the MyRe-
serve Command protective cover from below
•
leave at least 15 cm cable length inside the protective
cover
•
place the seal insert around the cables
•
close unused openings of the seal with the synthetic
seals
•
countersink the sealing insert in the cable branch col-
lector disc
•
Screw the cable collector disc tight (pliers or 41 mm
wrench required)
NOTE
Tightening of the cable branch should be stopped
when the seal insert forms a bead which protrudes
slightly over the union nut.
NOTE
NOTE
NOTE
•
Check the connectivity of the cables by gently tug-
ging on them
•
for less cable tension remove the insulation of the AC
cable approx. 15 cm behind the cable collector disc
NOTE
For outdoor installation: use weatherproof and fl e-
xible cables.
AC cable:
H07 RNF 3x1.5 mm
2
or alternatively with
outer diameter of 9.2 - 10.7 mm.
LAN/CAN cable:
minimum Cat5.e, outer diameter
6.0 - 6.5 mm, twisted pair cable
NOTE
NOTE
NOTE
1
AC cable (stripped), fl exible
2
LAN cable
3
CAN cable
4
cable branch seal insert
5
cable branch collector disc
1
2
3
4
remove AC cable insulation for 15 cm
5