Additional StorEdge Troubleshooting
Some of the troubleshooting procedure may require removing the covers of system components
(inverter, battery, StorEdge Connection Unit, or meter). Be sure to disconnect all power sources to avoid
electrocution.
For opening the cover refer to
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed.
Problem
Description or possible cause
Troubleshooting
During normal operation (grid
supplies power), no power to the
backup loads while the inverter is
producing power
The main circuit breakers or loads
circuit breakers in the backed up
loads panel have been triggered
Check that the backed-up loads
breakers on the CB panel are in the UP
position
Internal circuit breaker has been
triggered
Check that the AC circuit breaker in
the StorEdge Connection Unit is in the
UP position (see
)
The inverter is malfunctioning
Restart the inverter
If the problem persists, move the
AC bypass switch in the StorEdge
Connection Unit to position 2 (see
) to supply power to the loads
until the inverter problem is solved
(contact SolarEdge support if
required). Then move to position 1.
No power to the backup loads
while grid is OFF (power outage)
The backed-up loads are not
backed up
o
Check that the inverter is
producing power
o
Check that the Backup function is
enabled (
Backup conf
è
Backup
è
Enable
)
.
o
Check that there are no errors on
the inverter LCD
o
Check the circuit breakers on the
backed-up loads AC panel
o
Check that the AC breaker in the
StorEdge Connection Unit are in
the UP position (see
o
Check that the AC bypass switch
in the StorEdge Connection Unit is
set to position 1 (see
) .
SolarEdge
StorEdge
-Single
Battery/High
Capacity
Installation
MAN-01-00283-
1.1
86
Additional StorEdge Troubleshooting