4. Select
Meter 2
. The meter configuration screen is displayed (SolarEdge meters are pre-configured to
Device ID 2):
D e v i c e T y p e < M T R >
P r o t o c o l < W N >
D e v i c e I D < 2 >
C T R a t i n g < 0 >
M e t e r F u n c . < N o n e >
5. Configure the meter:
a. Select
Device Type
è
Revenue Meter
b. Select
Protocol
è
WattNode
c. Verify that
Device ID
is set to
2
.
d. Set the CT value that appears on the CT label:
CT Rating
è
<xxxxA>
.
If CT resets to 0, check the communication as described in step b of verify the connection:below.
e. For a meter installed at the grid connection point select
Meter Func.
è
Import.
E x p o r t + I m p o r t
E x p o r t
C o n s u m p t i o n
P r o d u c t i o n
I m p o r t
N o n e
The selected option is displayed in the RS485 Conf screen as <E+I>.
6. Select
Battery 1
. The battery configuration screen is displayed:
D e v i c e T y p e < B A T >
P r o t o c o l < T 7 4 >
D e v i c e I D < 2 4 >
B a t t e r y I n f o < >
7. Select
Device Type
è
Battery Pack
.
8. To verify battery connection, select
Battery Info
and check that the battery information is displayed.
If not, check the wiring to the battery:
S N : < s e r i a l # >
M o d e l : < X X X X X X >
R a t e d P W R [ k W H ] : N / A
F W V e r . < X X X X X >
Make sure to have the battery serial number and firmware version at hand whenever contacting
support.
SolarEdge
StorEdge
-Single
Battery/High
Capacity
Installation
MAN-01-00283-
1.1
68
Configuring the RS485 Bus for Battery and Meter Connection