L30US-IB80, L30US-IB00, L40US UPS
Figure 15 Cold start button
When the battery is working, rectifier starts operation, 30 seconds later inverter will start and
the battery LED will turn on.
CAUTION!
Press the cold start button after 30 seconds until closing the battery switch.
4.2.7.
Shutdown procedure
This procedure will be followed by complete shutdown the UPS and the load. After all power
switches, isolators and circuit breakers are opened, there will be no output.
1.
For L30US-IB80, L30US-IB00, shut down the inverter; navigate to common
→
inv on/off
→
single off (see 4.3.9.1).
2.
For L40US, turn OFF the BATTERY breaker.
3.
Turn OFF the MAINS breaker.
4.
Turn OFF the BYPASS breaker.
5.
Open the OUTPUT breaker. The UPS will shut down.
6.
To completely isolate the UPS from AC Mains, all input switches of Utility must be
completely off, which includes the ones for rectifier and bypass.
The primary input distribution panel is often located far away from the UPS area, so a
label should be posted to advise service personnel that the UPS circuit is under
maintenance.
Summary of Contents for L30US-IB00
Page 2: ......
Page 18: ...10 L30US IB80 L30US IB00 L40US UPS 3 5 Dimensions and Weight Figure 4 Dimensions...
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 51: ......
Page 52: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 58: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 78: ...4256 7784 C...