background image

 

Tripp Lite

1111 West 35th Street

Chicago, IL 60609 USA

Telephone: +(773) 869 1234

E-mail: 

[email protected]

Model Number: SMART700HG

SmartPro Medical Grade .7kVA 120V Line interactive Tower UPS, full isolation, USB & Serial ports

 

Highlights

700VA line interactive tower UPS

Maintains 120V nominal output over an input range of 82 to 142V

Professional features include serial port, hospital grade plug & outlets, built-in

isolation transformer and UL60601-1 listing

Input: NEMA 5-15P (120V 15A) / Output: 4 NEMA 5-15R (120V)

Leakage current less than 100 microamps

Description

 Tripp Lite's SMART 700HG offers medical-grade UPS protection with built-in line interactive voltage regulation, intelligent monitoring and
unattended shutdown capability. UL 60601-1 listed as medical electrical equipment. Built-in isolation transformer with Faraday shield removes
common mode noise while maintaining full AC surge suppression in all modes less than 100 microamps. Resistant to electrostatic discharge.
Includes high quality hospital-grade plug and outlets. 700VA power handling capacity supports computers, inter-networking equipment and other
critical loads during commercial power failures. Line interactive voltage regulation corrects brownouts as low as 81V and overvoltages as high as
143 back to normal 120V levels, saving battery reserves for use only during complete power failures. Includes 4 outlets, diagnostic LEDs and built-in
USB & RS-232 communications ports that work with downloadable PowerAlert Software and cabling to provide automatic unattended shutdown of
connected network and PC applications. 

Package Includes

SMART 700HG Medical Grade UPS System 

One USB and One DB9 monitoring cable

Warranty information 

Instruction manual

Features

Ideal UPS protection for applications in medical patient-care areas where UL 60601-1 listed medical electrical equipment is required

Built-in isolation transformer with Faraday shield offers full isolation and removes common mode noise while maintaining full AC surge

suppression in all modes

Line-interactive voltage regulation corrects brownouts and overvoltages from 81 to 143 volts back to usable 120V output levels, without

using battery power

Hospital-grade plug and outlets offer added degree of safety and reliability to input/output connections

Full line isolation offers a higher degree of safety and prevents operational problems in sensitive electronic equipment

Resistant to electrostatic discharge

Supports loads up to 700VA/450 watts

42 minutes half load runtime (with 350VA load), 18 minutes full load runtime (with 700VA load)

4 protected hospital-grade outlets; 6-ft. cord

RS-232 and USB monitoring ports for remote monitoring and unattended shutdown

PowerAlert unattended shutdown software available via free download from www.tripplite.com (cabling included)

Complete surge protection, line isolation and EMI/RFI noise filtering

5 diagnostic LEDs indicate AC present, on battery, voltage correction, overload & battery low/replace

Battery replacement door and back panel grounding lug

Summary of Contents for SMART700HG

Page 1: ...n USB RS 232 communications ports that work with downloadable PowerAlert Software and cabling to provide automatic unattended shutdown of connected network and PC applications Package Includes SMART 700HG Medical Grade UPS System One USB and One DB9 monitoring cable Warranty information Instruction manual Features Ideal UPS protection for applications in medical patient care areas where UL 60601 1...

Page 2: ...es Output AC waveform AC mode Sine wave Output AC waveform battery mode PWM sine wave INPUT Rated input current at maximum load 5 5A Nominal Input Voltage s Supported 120V AC UPS input connection type 5 15P HG Input circuit breaker 10A UPS Input cord length ft 6 UPS Input cord length m 1 8 Recommended Electrical Service 15A 120V Input cord length ft 6 Input cord length m 1 8 Phase Single Phase BAT...

Page 3: ... indicates power failure overload and low battery conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch once silenced alarm will re sound to indicate low battery status Switches 2 Switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppression joule rating 480 UPS AC suppression response time Instantaneous ...

Page 4: ...rees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 97 7 Battery mode BTU hr full load 189 1 AC mode efficiency rating 100 load 94 COMMUNICATIONS Communications interface USB DB9 Serial Network monitoring port description Supports detailed monitoring of UPS and site power conditions PowerAlert...

Page 5: ... lines 1 DTEL2 Network Surge Suppressor Essential protection for data and communication lines 1 UPSWM Wallmount Bracket and installation accessories 4 washers 4 screws 1 Velcro safety strap 1 WEXT3 500 1500 3 Year Extended Warranty For Smart Line Interactive and Online Tower or Rack models 1500VA or less 1 WEXT5 500 1500 5 Year Extended Warranty For Smart Line Interactive and Online Tower or Rack ...