Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail:
Model Number: SMART700HG
SmartPro Medical Grade .7kVA 120V Line interactive Tower UPS, full isolation, USB & Serial ports
Highlights
700VA line interactive tower UPS
Maintains 120V nominal output over an input range of 82 to 142V
Professional features include serial port, hospital grade plug & outlets, built-in
isolation transformer and UL60601-1 listing
Input: NEMA 5-15P (120V 15A) / Output: 4 NEMA 5-15R (120V)
Leakage current less than 100 microamps
Description
Tripp Lite's SMART 700HG offers medical-grade UPS protection with built-in line interactive voltage regulation, intelligent monitoring and
unattended shutdown capability. UL 60601-1 listed as medical electrical equipment. Built-in isolation transformer with Faraday shield removes
common mode noise while maintaining full AC surge suppression in all modes less than 100 microamps. Resistant to electrostatic discharge.
Includes high quality hospital-grade plug and outlets. 700VA power handling capacity supports computers, inter-networking equipment and other
critical loads during commercial power failures. Line interactive voltage regulation corrects brownouts as low as 81V and overvoltages as high as
143 back to normal 120V levels, saving battery reserves for use only during complete power failures. Includes 4 outlets, diagnostic LEDs and built-in
USB & RS-232 communications ports that work with downloadable PowerAlert Software and cabling to provide automatic unattended shutdown of
connected network and PC applications.
Package Includes
SMART 700HG Medical Grade UPS System
One USB and One DB9 monitoring cable
Warranty information
Instruction manual
Features
Ideal UPS protection for applications in medical patient-care areas where UL 60601-1 listed medical electrical equipment is required
Built-in isolation transformer with Faraday shield offers full isolation and removes common mode noise while maintaining full AC surge
suppression in all modes
Line-interactive voltage regulation corrects brownouts and overvoltages from 81 to 143 volts back to usable 120V output levels, without
using battery power
Hospital-grade plug and outlets offer added degree of safety and reliability to input/output connections
Full line isolation offers a higher degree of safety and prevents operational problems in sensitive electronic equipment
Resistant to electrostatic discharge
Supports loads up to 700VA/450 watts
42 minutes half load runtime (with 350VA load), 18 minutes full load runtime (with 700VA load)
4 protected hospital-grade outlets; 6-ft. cord
RS-232 and USB monitoring ports for remote monitoring and unattended shutdown
PowerAlert unattended shutdown software available via free download from www.tripplite.com (cabling included)
Complete surge protection, line isolation and EMI/RFI noise filtering
5 diagnostic LEDs indicate AC present, on battery, voltage correction, overload & battery low/replace
Battery replacement door and back panel grounding lug