background image

UPS / Power Module
dimensions in primary
form factor (height x width
x depth / cm)

32.4 x 19 x 22.9

UPS / Power Module weight
(lbs)

44.2

UPS / Power Module weight
(kg)

20.1

UPS Shipping dimensions
(height x width x depth /
inches)

18.2 x 11.8 x 13.5

UPS Shipping dimensions
(height x width x depth /
cm)

46.4 x 29.8 x 34.3

Shipping weight (lbs)

49

Shipping weight (kg)

22.2

Cooling method

Fan

UPS housing material

PVC

ENVIRONMENTAL

Operating Temperature
Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full
load)

97.7

Battery mode BTU / hr. (full
load)

189.1

AC mode efficiency rating
(100% load)

94%

COMMUNICATIONS

Communications interface

USB; DB9 Serial

Network monitoring port
description

Supports detailed monitoring of UPS and site power conditions

PowerAlert software

Included

Communications cable

USB and DB9 serial cabling included

LINE / BATTERY TRANSFER

Transfer time

2-4 milliseconds

Low voltage transfer to
battery power (setpoint)

81

High voltage transfer to
battery power (setpoint)

143

SPECIAL FEATURES

Grounding lug

Grounding lug

Summary of Contents for SMART700HG

Page 1: ...n USB RS 232 communications ports that work with downloadable PowerAlert Software and cabling to provide automatic unattended shutdown of connected network and PC applications Package Includes SMART 700HG Medical Grade UPS System One USB and One DB9 monitoring cable Warranty information Instruction manual Features Ideal UPS protection for applications in medical patient care areas where UL 60601 1...

Page 2: ...es Output AC waveform AC mode Sine wave Output AC waveform battery mode PWM sine wave INPUT Rated input current at maximum load 5 5A Nominal Input Voltage s Supported 120V AC UPS input connection type 5 15P HG Input circuit breaker 10A UPS Input cord length ft 6 UPS Input cord length m 1 8 Recommended Electrical Service 15A 120V Input cord length ft 6 Input cord length m 1 8 Phase Single Phase BAT...

Page 3: ... indicates power failure overload and low battery conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch once silenced alarm will re sound to indicate low battery status Switches 2 Switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppression joule rating 480 UPS AC suppression response time Instantaneous ...

Page 4: ...rees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 97 7 Battery mode BTU hr full load 189 1 AC mode efficiency rating 100 load 94 COMMUNICATIONS Communications interface USB DB9 Serial Network monitoring port description Supports detailed monitoring of UPS and site power conditions PowerAlert...

Page 5: ... lines 1 DTEL2 Network Surge Suppressor Essential protection for data and communication lines 1 UPSWM Wallmount Bracket and installation accessories 4 washers 4 screws 1 Velcro safety strap 1 WEXT3 500 1500 3 Year Extended Warranty For Smart Line Interactive and Online Tower or Rack models 1500VA or less 1 WEXT5 500 1500 5 Year Extended Warranty For Smart Line Interactive and Online Tower or Rack ...

Reviews: