19
L30US-IB80, L30US-IB00, L40US UPS
NOTE!
When the voltage level is 120V, the value range is 10%, 15%, 20%, 25%, and
20% (default).
When the voltage level is 127 V, the value range is 10%, 15%, and 20% (default).
4.2.3.
Maintenance bypass
To supply the load by mains, you may simply activate the internal mechanical bypass switch.
CAUTION!
The load is not protected by the UPS when the internal mechanical bypass
system is active, and the power is not conditioned.
4.2.4.
Switch to mechanical bypass
CAUTION!
In case the UPS is running normally and can be controlled through the display,
carry out steps 1 to 6; otherwise, jump to Step 5.
1.
At this time, the bypass source will supply. Navigate to Common>INV ON/OFF>Single
OFF, open the cover of maintenance switch, the UPS switches to bypass mode
automatically.
2.
Turn on MAINTENANCE breaker.
3.
Turn OFF the MAINS breaker.
4.
Turn OFF the BYPASS breaker.
5.
Turn OFF the OUTPUT breaker.
The load will be fed through the MAINTENANCE breaker.
4.2.5.
Switch to normal operation (from mechanical bypass)
Summary of Contents for L30US-IB00
Page 2: ......
Page 18: ...10 L30US IB80 L30US IB00 L40US UPS 3 5 Dimensions and Weight Figure 4 Dimensions...
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 51: ......
Page 52: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 58: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 78: ...4256 7784 C...