L30US-IB80, L30US-IB00, L40US UPS
4.3.7.2.
Parallel setting
CAUTION!
Only two UPS systems of this model can be connected in a parallel system.
Parallel ID:
Parallel ID, must modify the ID after setting work mode to parallel mode. The
value can be 1 to 2, default value is 1, maximum allowed value is 2, because only two
UPSes of this model can be connected in a parallel system.
Cabinet Parallel Basic Units:
Parallel cabinet number, must modify the total parallel
cabinet number after setting work mode to parallel mode. The value can only be 2,
because only two UPS systems of this model can be connected in a parallel system.
Cabinet Parallel Redundancy Units:
Parallel redundancy cabinet number, can modify the
redundancy cabinet number after set work mode to parallel mode. The value can be 0~1,
default value is 0, maximum allowed value is 1, because only two UPS systems of this
model can be connected in a parallel system.