40
L30US-IB80, L30US-IB00, L40US UPS
4.3.6.7.
Bypass settings
Bypass Volt Prot. Lower Limit:
When the difference between the bypass voltage and the
rated voltage exceeds the lower threshold for the bypass voltage, the system determines that
the bypass voltage is abnormal and that the bypass is unavailable. The value can be –10%, –
15%, –20%, –30%, –40%, The default value is –30%.
Bypass Volt Prot. Limit:
When the difference between the bypass voltage and the rated
voltage exceeds the upper threshold for the bypass voltage, the system determines that the
bypass voltage is abnormal and that the bypass is unavailable.
NOTE!
When the voltage level is 120V, the value range is 10%, 15%, 20%, 25%,
and 20% (default).
When the voltage level is 127 V, the value range is 10%, 15%, and 20%
(default).
Bypass Freq Tracking Range: When the difference between the bypass input frequency and
the rated frequency exceeds this value, the system determines that the bypass frequency is
not normal, and that the bypass is unavailable. The value range is
±
1%,
±
2%,
±
4%,
±
5%,
±
10%(default).
Bypass Rate Tracking Rate:
Inverter frequency tracking to bypass frequency rate. The value
range is 0.5~2Hz/s and is 1 by default.
Summary of Contents for L30US-IB00
Page 2: ......
Page 18: ...10 L30US IB80 L30US IB00 L40US UPS 3 5 Dimensions and Weight Figure 4 Dimensions...
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 51: ......
Page 52: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 58: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 78: ...4256 7784 C...