1
MASTERYS IP+
60-80 kVA 3/3
ENGLISH
IOMMASIPXX08-GB 02
51
TECHNICAL SPECIFICATIONS
12
Models
60
80
Input/Output phases
3/3
3/3
Electrical specifi cations - Input
60
80
Mains voltage
3P+N 400 V ±20% (up to -35% @70% of nominal load)
Input frequency
50-60 Hz ±10%
Input power factor
0,99
THDI <
3%
Electrical specifi cations - Output
60
80
Output voltage (P+N)
230 V single phase (selectable: 208*/220/230/240 V) ±1%
Frequency
50-60 Hz ±2% (from 1% to 8% if generator is used)
Automatic bypass
nominal output voltage ±15%
(from 10% to 20% selectable if generator is used)
Nominal power (kW)
48
64
Overload on mains power supply
125% 10 minutes
150% 1 minute
Crest factor
3:1
Voltage distortion
1% with linear load
* @ Pout = 90% Pnom
Environment
60
80
Operating temperature
0÷35 °C (15÷25 °C recommended for longer battery life)
Storage temperature
-5÷45 °C
Relative humidity
0÷95% condensation-free
Max. altitude
1.000 m (3.300 ft) without derating; 3.000 m (10.000 ft) max
Acoustic noise (dB)
< 62
< 62
Required cooling capacity (m
3
/h) 1810
1810
Dissipated power max (W)
6100
8100
Dissipated power (BTU/h)
20820
27640
Standards
60
80
Safety
EN 62040-1-1, EN 60950-1
Type and performance
EN 62040-3 (VFI-SS-111)
EMC EN
62040-2
Product certifi cation
Protection level
IP31
1000
835
1.400
Weight:
- 60 kVA: 530 kg
- 80 kVA: 600 kg