MODES OF OPERATION
4.1 ON LINE OPERATIONS.
A special feature of the MASTERYS™ series is the “ON LINE” double conversion feature in conjunction with low dis-
tortion mains power absorption. With ON LINE mode, the UPS is able to supply a voltage that is fully stabilised in
frequency and amplitude, regardless of any interference in the mains power supply within the most stringent clas-
sifi cation of UPS regulations.
ON LINE operation provides three operating modes according to mains and load conditions:
•
“Normale” mode
.
This is the most frequent operating condition: the energy is drawn from the primary mains power supply and is
converted and used by the inverter to generate the output voltage to power the loads connected.
The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an
overload or inverter shutdown) without any break in the power supply to the load.
The battery charger supplies the energy required to maintain or recharge the battery.
•
“Bypass” mode
.
In case of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in
the power supply. This procedure may occur in the following situations:
- in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS
output is switched onto the auxiliary mains via the automatic bypass. Normal operation, which is from inverter,
returns automatically a few seconds after the overload disappears.
- when the voltage generated by the inverter goes is out of tolerances due to a major overload or a fault on the
inverter.
- wWhen the internal temperature exceeds the maximum value allowed.
•
“Battery” mode
.
In the event of a mains failure (micro interruptions or extended black-outs), the UPS continues to power the load
using the energy stored in the battery. The Expert Battery System keeps the user constantly informed on the
battery status and on the back-up time available. The disconnection of non mission critical applications during
battery discharge can be programmed (after a certain laps of time) by using the Power Share option, so that the
battery resources can be reserved for the most critical applications.