1
MASTERYS IP+
60-80 kVA 3/3
ENGLISH
IOMMASIPXX08-GB 02
17
UNPACKING AND INSTALLATION
OF THE UNIT
3
3.10 ADC CARD.
This card can be confi gured to control up to four outputs that are normally closed or normally open and up
to three digital inputs. The card is inserted in one of two slots provided (refer to 3.5 “Identifying switching and
connection organs”) .
3.10-1
A
2
3
4
1
OUT
OUT
0 1 2 P3
C2
NO2
NC2
IN1-
IN1+
IN3-
IN3+
C3
NO3
NC3
C1
NO1
NC1
IN1-
IN1+
IN2-
IN2+
C4
NO4
NC4
OUT1
OUT2
DIP1 DIP2
IN3
OUT3
IN1
IN2
OUT4
Up to four operating modes can be selected using the two DIP switches 1 or 2.
• The fi lter level indicates:
1
immediate activation (1 seconds minimum communication time) -
2
10 s delay -
3
30 s delay.
Mode 1 - STANDARD confi guration
Position
IN/OUT
Description
Filter
dip1 dip2
level
OFF OFF
Out 1
General Alarm
2
OFF OFF
Out 2
Battery discharging
3
OFF OFF
Out 3
Battery low or
2
imminent stop
OFF OFF
Out 4
UPS on by-pass
2
OFF OFF
In
1
*
E.S.D.
1
OFF OFF
In 2
Supply from GenSet
1
OFF OFF
In 3
Isolation controller
2
Mode 2 - POWER SAFE confi guration
Position
IN/OUT
Description
Filter
dip1 dip2
level
ON OFF
Out 1
General Alarm
2
ON OFF
Out 2
Power safe plug 1
2
ON OFF
Out 3
Power safe plug 2
2
ON OFF
Out 4
Power safe plug 3
2
ON OFF
In 1
*
E.S.D.
1
ON OFF
In 2
Supply from GenSet
1
ON OFF
In 3
Management of
1
energy
consuption
Mode 3 - SAFETY confi guration
Position
IN/OUT
Description
Filter
dip1 dip2
level
OFF ON
Out 1
General Alarm
2
OFF ON
Out 2
E.S.D. activation
1
OFF ON
Out 3
Battery low or
2
imminent
stop
OFF ON
Out 4
E.S.D. activation
1
OFF ON
In
1
*
E.S.D.
1
OFF ON
In 2
External alarm A39
2
OFF ON
In 3
External alarm A40
2
Mode 4 - ENVIRONMENTAL confi guration
Position
IN/OUT
Description
Filter
dip1 dip2
level
ON
ON
Out 1
General Alarm
2
ON
ON
Out 2
Over-heating
2
ON
ON
Out 3
Overload /
2
Loss of redundancy
ON
ON
Out 4
External alarm In2
2
ON
ON
In 1
*
E.S.D.
1
ON
ON
In 2
External alarm A39
2
ON
ON
In 3
External alarm A40
2
*
if the external E.S.D. button is not used, always insert a jumper to short circuit input IN 1 (Figure 10.1-1).
OUT1
IN2
OUT4
OUT2
OUT3
IN3
DIP1 2
IN1