MASTERYS IP+
60-80 kVA 3/3
IT
ALIANO
ENGLISH
48
IOMMASIPXX08-GB 02
10.3 PREVENTIVE MAINTENANCE.
All operations on the equipment must be carried out solely by SOCOMEC UPS personnel or by
authorised service personnel.
Maintenance requires accurate functionality checks of the various electronic and mechanical parts and, if necessary,
the replacement of parts subject to wear and tear (batteries, fans and condensers). It is recommended to carry out
periodic specialised maintenance (annually), in order to keep the equipment at the maximum level of effi ciency and
to avoid the installation being out of service with possible damage/risks. Moreover, attention should be paid to any re-
quests for preventive maintenance that the equipment may automatically display with alarm/warning message M29.
10.3.1 Batteries.
The state of the battery is fundamental to UPS operation.
Thanks to the
Expert Battery System
, the information relating to the state and the conditions of use of the battery
are processed in real time and the recharging and discharging procedures are selected automatically in order to
optimise battery life expectancy and off er maximum performance.
Furthermore, during the operating life of the battery, MASTERYS™ stores statistics on the conditions of use of the
battery for analysis.
Since the expected life of the batteries is very much dependent on operating conditions (number of charging and
discharging cycles, load rate, temperature), a periodic check by authorised personnel is recommended.
When replacing the batteries, use the same type and confi guration by placing them in the appro-
priate containers so as to avoid the risk of acid leakage.
The replaced batteries must be disposed of at authorised recycling and disposal centres.
Do not open the plastic cover of the batteries as they contain harmful substances.
10.3.2 Fans.
The life of the fans used to cool the power parts is dependent on the using and environmental conditions (tem-
perature, dust).
Preventive replacement by an authorised technician is recommended within four years (in normal operating condi-
tions).
When needed, fans must be replaced as per specifi cations by SOCOMEC UPS.
10.3.3 Capacitors.
The equipment houses electrolytic capacitors (used in the rectifi er and inverter section) and fi ltering capacitors
(used in the output section), whose life is dependent on using and environmental conditions.
The average expected life of these components is shown below:
• Electrolytic capacitors: 5 years;
• Filtering capacitors: 7 years.
In any case the eff ective state of the components is verifi ed during preventive maintenance.
PROBLEM SOLVING
10
Summary of Contents for MASTERYS IP+ 60
Page 1: ...INSTALLATION AND OPERATING MANUAL MASTERYS IP 60 80 kVA 3 3...
Page 2: ......
Page 52: ......
Page 53: ...PARALLEL 1 1 REDUNDANT CONFIGURATION MASTERYS IP 60 80 kVA 3 3...
Page 57: ......
Page 58: ......
Page 59: ......