MASTERYS IP+
60-80 kVA 3/3
IT
ALIANO
ENGLISH
46
IOMMASIPXX08-GB 02
The alarm messages displayed enable an immediate diagnosis.
Alarms are divided into two categories:
• Alarms related to the UPS external circuits: input mains, output mains, temperature and environment.
• Alarms related to the UPS internal circuits: in this case, the corrective actions will be carried out by the After Sales
Department.
10.1 SYSTEM ALARMS.
• A02: output overload
.
The power required by the loads is higher than the power available.
Check that the load is well balanced on the three phases by checking the measurements on the display. If needed,
disconnect any loads that do not need uninterruptible power.
Important!
The accepted overload time limit is defi ned in the technical specifi cations. When this time limit is exceeded, the
loads will no longer be powered by the inverter.
• A06: auxiliary mains out of tolerance
.
The auxiliary mains exceeds the acceptable tolerance values. Possible causes are:
• No voltage or frequency present or voltage and frequency out of acceptable values (see the technical specifi ca-
tions).
• The frequency is subject to continuous variations (typical with power supplied from an incorrectly sized GE).
• A07: temperature over the limits.
The technical plant temperature is higher than the maximum value recommended.
Check the ventilation or air conditioning system in the UPS room.
• A08: maintenance bypass activated.
The Q5 maintenance bypass switch Q5 is closed.
The load is therefore powered directly by mains power supply. See Chapter 7.4.
• A17: improper conditions of use.
This alarm does not indicate a malfunction or failure of the UPS, but an incorrect use/sizing of the system. It is
activated in the event of:
• Operation for long periods at high temperatures (battery deterioration)
• High number of overloads (wrong sizing)
• Continuous battery discharging (mains not stable)
• High number of switches onto the bypass (high impulsive loads)
• A22: input mains out of tolerance.
The input mains is not present or not suffi cient (voltage and/or frequency values incorrect with reference to the
technical data); if there is no input mains outage, check if no protections upstream of the UPS have tripped. Check
that the voltage applied and frequency values are in compliance with the values set on the mimic panel.
• A38, A39, A40, A41: external alarm 1, 2, 3, 4.
One of the ADC PCB inputs has been activated; check the situation of the devices connected to this PCB.
10
PROBLEM SOLVING
Summary of Contents for MASTERYS IP+ 60
Page 1: ...INSTALLATION AND OPERATING MANUAL MASTERYS IP 60 80 kVA 3 3...
Page 2: ......
Page 52: ......
Page 53: ...PARALLEL 1 1 REDUNDANT CONFIGURATION MASTERYS IP 60 80 kVA 3 3...
Page 57: ......
Page 58: ......
Page 59: ......