IT
ALIANO
ENGLISH
36
IOMMASGPXX01-GB_01
10-40 kVA
6.1.3.3 “Commands” menu.
This is used to send some immediate commands to activate the UPS or various operating modes. It can also be used
to send extended commands to define some UPS settings.
To activate the commands select the command with
UP
or
DOWN
, press
ENTER
, select
YES
or
NO
to
execute and press
ENTER
to confirm.
“Extended commands”.
They can only be displayed if the extended commands item in the configurations menu has been activated.
IMMEDIATE COMMANDS menu
Command Description
START PROCEDURE
UPS start-up command.
STOP PROCEDURE
UPS shutdown command.
MAINTENANCE BY-PASS
Control to activate the manual bypass and shutdown of the UPS.
PROCEDURE
HIGH EFFICIENCY MODE
Activates Eco mode / always on mode.
NORMAL MODE
Activates normal double conversion operation.
ALARM RESET
Resets all the alarms.
LEDS TEST
Performs the test on the mimic panel LEDs.
EXTENDED COMMAND menu
Command Description
MANUAL BATTERY TEST
Activates the battery test.
BATTERY COMMISSION
Activates battery commissioning (use only if necessary for the type of battery).
SET LAN DEFAULT VALUE
Resets all the values of the LAN.
JBUS TUNNELING ENABLE
Enables the connection of advanced software (BMS or Uni vision) via the LAN network.
JBUS TUNNELLING DISABLE
DHCP ENABLE
Enables the automatic allocation of the IP address by the network server.
DHCP DISABLE
FORCE MODEM DIAL OUT
Forces sending of an immediate test modem call.
ENERGY SAVER ENABLE
Enables energy save mode on a parallel system.
ENERGY SAVER DISABLE
DISABLE CHECK-UP
Deactivates the periodic maintenance message (visible only if alarm A44 is present).
MIMIC PANEL
6
Summary of Contents for Masterys Green Power
Page 1: ...INSTALLATION AND OPERATING MANUAL IOMMASGPXX01 GB_01 10 40 kVA...
Page 2: ...ITALIANO...
Page 62: ......