ENGLISH
IOMMASGPXX01-GB_01
15
10-40 kVA
3
UNPACKING AND INSTALLATION
OF THE UNIT
3.5-1
3.5-2
Set
Q1
,
Q2
and
Q6
to the 0 position.
Q1
Q2
Q6
EXT. BATTERY
OUTPUT
MAINS SUPPLY
L12 L22 L32 N2
L11 L1 L21 L2 L31 L3 N11 N1
+B2 -B2 -B1 +B1
OUTPUT
L12
L22
L32
N2
MAINS
N1
L3
L2
L1
3/3
Connections
if
THE MAINS AND AUX MAINS ARE CONNECTED IN COMMON
3.5
INSTALLATION PROCEDURES AND INSTRUCTIONS
.
WARNING!
Before carrying out work on the terminal board or on UPS internal parts, ensure that the UPS is
switched off, remove the power supply, open the external battery cabinet disconnectors, isolate
the system and wait 5 minutes.
$BCMFTQFDJöDBUJPOT
r TUSJQQJOHMFOHUINN
r UJHIUFOJOHUPSRVF/N