10-40 kVA
COMMUNICATION
8
8.2 STANDARD LAN WEB PAGE.
By connecting the UPS to a standard LAN network, the operating status of the UPS can be monitored from any PC
connected to the network through an html page.
8.2.1 Activation.
Comply with the following operations to activate the monitoring system:
r $POOFDUUIF614UPUIF-"/OFUXPSL DPOOFDUPS
C3
in Fig. 8.2.1-1).
A. If the BOOT DHCP protocol is enabled in the local network: verify the IP address shown in the
PARAMETERS
>
PRESENT CONFIG
>
LOCAL AREA NETWORK IP
menu on the UPS mimic panel (go to point C).
B. If the BOOT DHCP protocol is not enabled in the local network:
Foreword: the following is applicable only if the user is in possession of the administrator rights, otherwise the
procedure indicated below is only valid if using a stand-alone PC (i.e. not in a network of computers with admin-
istrator privileges) and a network twisted cable.
Deactivate DHCP mode in the
COMMAND
>
EXT.COMMAND
>
DHCP DISABLE
menu on the UPS mimic
panel.
Read the IP address given in the
PARAMETERS
>
PRESENT CONFIG
>
LOCAL AREA NETWORK IP
menu
on the UPS mimic panel (by default 192.168.7.19).
From a PC connected to the network add the address read by means of the following command: Route add
192.168.7.19 210.67.192.147 (assuming 210.67.192.147 to be the IP address of the PC being used).
C. Open an internet browser and key in the address http://XXX.XXX.XXX.XXX and press send (where xxx.xxx.xxx.xxxx
is the IP address read on the mimic panel).
8.2.1-1
C3