PROBLEM SOLVING
9
."45&3:4JOPSEFSUPPíFSPQUJNVNPQFSBUJOHFîDJFODZBOEBWPJEEPXOUJNFPGUIFFRVJQNFOU
It is strongly recommended to give due consideration to any requests for preventive maintenance automatically
displayed with alarm message M29 (refer to paragraph 6.2.3.1).
All operations on the equipment must be only carried out by SOCOMEC UPS personnel or by authorised support
personnel.
Maintenance consists of accurate functional checks on electronic and mechanical parts with replacement of parts
TVCKFDUUPXFBSJGOFDFTTBSZ UZQJDBMMZCBUUFSJFTGBOTBOEDBQBDJUPST
9.3.1 Batteries.
The state of the battery is fundamental to UPS operation.
Thanks to the
Expert Battery System
, the information relating to the state and the conditions of use of the battery
are processed in real time and the recharging and discharging procedures are selected automatically in order to
PQUJNJTFCBUUFSZMJGFFYQFDUBODZBOEPíFSNBYJNVNQFSGPSNBODF
'VSUIFSNPSFEVSJOHUIFPQFSBUJOHMJGFPGUIFCBUUFSZ."45&3:4TUPSFTTUBUJTUJDTPOUIFDPOEJUJPOTPGVTFPGUIF
battery for analysis.
Since the expected life of the batteries is very much dependent on operating conditions (number of charging and
discharging cycles, load rate, temperature), a periodic check by authorised personnel is recommended.
8IFOSFQMBDJOHUIFCBUUFSJFTVTFUIFTBNFUZQFBOEDPOöHVSBUJPOCZQMBDJOHUIFNJOUIFBQQSP
-
priate containers so as to avoid the risk of acid leakage.
The replaced batteries must be disposed of at authorised recycling and disposal centres.
Do not open the plastic cover of the batteries as they contain harmful substances.
9.3.2 Fans.
The life of the fans used to cool the power parts is dependent on the using and environmental conditions (tem-
perature, dust).
Preventive replacement by an authorised technician is recommended within four years (in normal operating condi-
tions).
8IFOOFFEFEGBOTTIPVMECFSFQMBDFEBTQFSTQFDJöDBUJPOTCZ40$0.&$614
9.3.3 Capacitors.
The equipment houses electrolytic capacitors (used in the rectifier and inverter section) and filtering capacitors
(used in the output section), whose life is dependent on using and environmental conditions.
The average expected life of these components is shown below:
r &MFDUSPMZUJDDBQBDJUPSTZFBST
r 'JMUFSJOHDBQBDJUPSTZFBST
*OBOZDBTFUIFFíFDUJWFTUBUFPGUIFDPNQPOFOUTJTWFSJñFEEVSJOHQSFWFOUJWFNBJOUFOBODF