ENGLISH
IOMMASGPXX01-GB_01
31
10-40 kVA
MIMIC PANEL
6
Meaning of ideograms
Code Description
Condition
M1
Load on bypass, in Eco-mode or Maintenance bypass closed
Steady
Automatic bypass alarm
Flashing
M2
Input rectifier active.
Steady
Input rectifier general alarm.
Flashing
M3 Battery
OK.
Steady
Battery
alarm.
Flashing
M4-M7
Remaining battery capacity.
Steps of 25%
Battery recharging.
Sequence M7 M4
M8 Inverter
on
Steady
Inverter general alarm.
Flashing
M9
Output voltage present.
Steady
M10
Input mains OK.
Steady
Input mains alarm.
Flashing
M11 Inverter
on.
Steady
M12
Module 1 present.
Steady
Module 1 general alarm.
Flashing
M13
Module 2 present.
Steady
Module 2 general alarm.
Flashing
M14
Module 3 present.
Steady
Module 3 general alarm.
Flashing
M15
Module 4 present.
Steady
Module 4 general alarm.
Flashing
M16
Module 5 present.
Steady
Module 5 general alarm.
Flashing
M17
Module 6 present.
Steady
Module 6 general alarm.
Flashing
M18 Load
present.
Steady
Overload.
Flashing
M19-M28
Output load indicator.
Steps of 10%
M29
Periodic maintenance alarm/warning.
Flashing
M30
Activation code alarm.
Steady
General
alarm.
Flashing
M31
LAN connection ready (Cable Connected).
Steady
Summary of Contents for Masterys Green Power