13.8.
Emergency breaking (trip function)
The emergency breaking (trip) function ensures the following:
- on-load breaking,
- breaking across all live conductors.
The product must be configured and wired as follows to allow emergency breaking:
207208209210
43 44 53 54 63 64 73 74
Menu
Parameters
Setting
SETUP
2ND TRIP
YES
I-O
IN1
FT1
I-O
IN1
NO
I-O
IN2
RST
I-O
IN2
NO
Following an emergency trip, the fault must be validated and inhibited to allow the resumption of automatic
operation (by opening then closing the Auto-Man cover, activating the RST input or via the RS485).
The solution shown above enables resetting via activation of the RST input.