13.4.5.1. Error messages list
Error message
Definition
Action
Reset
1
2
Duty cycle
Limited number of operations in a
defined period.
Wait 1 min. for the error message
to disappear.
Automatic
1
2
Source
I
/source
II
neutral wiring mismatch
The neutral on source
I
is not
wired on the same side as the
neutral on source
II
.
Rewire one of the two sources.
E.g. both neutrals on the left, or
both neutrals on the right.
Open and then close the
cover
1
2
1
2
Source
I
/
source
II
fault
This fault only appears if input
FT1/FT2 (see I-O Menu) and the
parameter 2ND TRIP (see Setup
Menu) are activated. Activation
of this fault shifts the changeover
switch to position 0.
Resolve the external problem that
caused activation of input FT1/
FT2
Open and then close the
cover or activate the RST
input, if configured (see
I-O Menu) or via RS485.
1
2
1
2
Alarm 1 / Alarm 2
This fault only appears if input AL1/
AL2 is activated (see I-O Menu).
Resolve the external problem that
caused activation of input AL1/AL2.
Once this is done, the error
message will automatically
disappear.
Automatic
1
2
1
2
Phase rotation fault on source
I
/source
II
The phase rotation does not
correspond to the ROT PH.
variable in the Setup menu.
Either invert two phases on
source
I
/ source
II
, or change
the status of the ROT PH. variable
in the Setup menu, if both sources
are faulty.
Automatic
1
2
1
2
Return to zero capacitor charging fault on source
I
/source
II
Recharging malfunction of
capacitor associated with source
I
/ source
II
.
Provisional action: deactivate the
RETURN 0 function in the Setup
menu (Set to NO), or open the
cover and operate manually.
Then: contact your retailer.
Open and then close the
cover
1
2
1
2
Insufficient switchover power on source
I
/source
II
The power is insufficient to leave
position II/I.
Supply the power (U,I) from source I
or II for at least 20 secs or open the
cover and operate manually.
Open and then close the
cover
1
2
1
2
1
2
Fault position 0, I, II
Following an electric or automatic
order, position 0 / I / II is not
reached.
Provisional action: open the Aut/
Man cover and operate manually.
Then: contact your retailer.
Change source status.
Manual operation.
1
2
Source starting timeout
II
If the genset does not start after
the 2ST delay, the message will be
sent.
Press the validation key.
Check that 2ST is greater than 15s
at 2AT.
Check the genset.