![socomec ATyS p M Instruction Manual Download Page 16](http://html1.mh-extra.com/html/socomec/atys-p-m/atys-p-m_instruction-manual_1311372016.webp)
16
EN
ATyS p M - 542935E - SOCOMEC
6. TECHNICAL DATA
Ratings
40A
63 A
80 A
100 A
125 A
160 A
Frequencies
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Thermal current Ith at 40 °C (A)
40
63
80
100
125
160
Thermal current Ith at 50 °C (A)
40
63
80
100
110*
125
Thermal current Ith at 60 °C (A)
40
50
63
80
100*
125
Thermal current Ith at 70 °C (A)
40
40
50
63
80*
100
Rated assigned insulation voltage Ui (V) (Power
circuit)
800
800
800
800
800
800
Rated impulse withstand voltage U
imp
(kV) (power circuit)
6
6
6
6
6
6
Rated insulation voltage U
i
(V) (control circuit)
300
300
300
300
300
300
Rated impulse withstand voltage U
imp
(kV) (control circuit)
2.5
2.5
2.5
2.5
2.5
2.5
Rated operational
currents (A)
IEC 60947-3 at 415 VAC
at 40 °C
AC 21A / 21 B
40/40
63/63
80/80
100/100
125/125
160/160
AC 22A / 22 B
40/40
63/63
80/80
100/100
125/125
125/160
AC 23A / 23 B
40/40
63/63
80/80
100/100
125/125
125/160
Rated operational
currents (A) IEC 60947-6-
1 415Vac at 40 °C
AC 33B / AC32B
**AC 33iB
40/40
63/63
80/80
100/100
125/125 125**/160
Fuse protected short-
circuit withstand if using
gG DIN fuses
Fuse protected short-
circuit withstand (kA eff)
50
50
50
50
50
40
Associated fuses (gG DIN)
40
63
80
100
125
160
Short-circuit capacity
Rated short-term
withstand current: Icw 1s
(kA eff)
4
4
4
4
4
4
Rated short-term
withstand current: Icw
30ms (kA eff)
10
10
10
10
10
10
Switching time at In
excluding loss of supply
sensing time and
excluding any delay
timers applicable.
I-II or II-I (ms)
180
180
180
180
180
180
Duration of “electrical
blackout” at Un (ms)
90
90
90
90
90
90
I-O / O-I / II-O / O-II (ms)
45
45
45
45
45
45
Consumption
Inrush current(A)
20
20
20
20
20
20
Consumption in stabilised
state (VA)
6
6
6
6
6
6
Mechanical
characteristics
Number of changeovers
10000
10000
10000
10000
10000
10000
Connection cross-section
(
not compatible with
aluminium cables)
Minimum size (Cu mm²),
flexible and rigid
10
10
10
10
10
10
Maximum size (Cu mm²),
flexible and rigid
70
70
70
70
70
70
Equipment class (According to IEC 60947-6-1)
PC
PC
PC
PC
PC
PC
EMC environment
A
A
A
A
A
A
* Possibility of reaching 125A with bigger connection cross-sections and use of the 160A bridging bar.
** AC 33iB 160A according to GB 14048.11.
This is a class A product. In a domestic environment, this product may cause radio interference in
which case the user may be required to take adequate measures.