46
EN
ATyS p M - 542935E - SOCOMEC
13.5.9. TIMERS Menu
Definition
Adjustment
range
Default
values
M-G* M-M*
1
2
1FT
Source
I
loss time delay (source
I
F
ailure
T
imer)
When source
I
disappears, 1FT is started. If source
I
is restored before the end of 1FT, the switchover cycle is
not engaged.
from:
- 0 to
3600 s
in M-M
- 0 to 60 s
in M-G
3 s
•
•
1
2
1RT Source
I
restoration time delay (source
I
R
eturn
T
imer)
When source
I
reappears, 1RT is started. At the end
of 1RT, source
I
is considered present. If source
I
disappears before the end of 1RT, the switchover is not
executed. If the replacement source disappears during
1RT, the latter dynamically and temporarily adopts the 3 s
setting value.
from 0 to
3600 s
180 s
•
•
1
2
10T Return to zero time delay from source
I
(source
I
to
0 T
imer)
Only accessible if the Setup menu parameter RETURN
0 is activated. Waiting time delay following source
I
failure, before switchover to position 0. This time delay
avoids opening directly to short-circuit or load impact.
from 0 to
10 s
2 s
•
•
1
2
2FT
Source loss time delay
II
(source
II
F
ailure
T
imer)
When source
II
disappears, 2FT is started. If source
II
is restored before the end of 2FT, the switchover cycle is
not engaged.
from 0 to
60 s
3 s
•
1
2
2RT Source
II
restoration time delay (source
II
R
eturn
T
imer)
When source
II
reappears, 2RT is started. At the end
of 2RT, source
II
is considered present. If source
II
disappears before the end of 2RT, the switchover is not
executed.
from 0 to
3600 s
5 s
•
1
2
2AT Stabilisation time delay (source
II
A
vailable
T
imer)
Stabilisation time delay for voltage and frequency on
Source
II
. The time delay starts as soon as the source
voltage is above the hysteresis value. This time delay must
be completed to enable transfer to Source
II
from 0 to
3600 s
5 s
•
1
2
2CT genset cooling time (source
II
) (source
II
C
ool Down
T
imer)
Following a switchover sequence, and after returning to
source
I
, source
II
(genset) is kept running for 2CT to
enable it to cool down.
from 0 to
600 s
180 s
•
1
2
20T Return to zero time delay from source
II
(source
II
to
0 T
imer)
Only accessible if the Setup menu parameter RETURN
0 is activated. Waiting time delay following source
II
failure, before switchover to position 0. This time delay
avoids opening directly to short-circuit or load impact.
from 0 to
10 s
10 s
•
•
* M-G : Mains - genset application - M-M : Mains - Mains application
• = timer present on M-G and/or M-M applications