background image

SMC Smoke Detector Guide 

 

 Copyright 

©

2011 SMC Networks

  

Page 6 

 

All Rights Reserved 

 

continued on next page 

Note:

 

Use only new batteries when replacing 

old batteries. Do not replace with batteries that 

were used previously. 

D. 

Observe correct polarity and insert two new 

3V lithium batteries into the battery 

compartment and replace the cover.  

B. 

Slide the battery compartment cover away 
from the smoke detector to unsnap it and 

lift it off (see the figure on page 3). 

Use only 3V lithium CR123A batteries, as listed 
on the battery compartment cover. 

A. 

Remove the smoke detector from the 
mounting base (see “Mounting Base 

Instructions” on page 7). 

C. 

Remove and dispose of the batteries 
appropriately. 

E. 

Reattach the smoke detector to the 

mounting base and test the system. 

Replacing Batteries 

B. 

When the Technician Settings menu appears, 
select Sensors & Zones > Sensor 

Diagnostics

The Sensor Diagnostic for <Security Zone name> 

appears as the system detects the current signal 

strength between the selected sensor and the 
TouchScreen. 

Test the smoke detector in place annually using 
Smoke! in a can® (product number SM-200), a 

canned aerosol simulated smoke and follow the 
directions on the can. 

C. 

When the currently installed sensors/ 
security zones appear, tap the zone you 

want to test for connectivity and follow the 
instructions from the TouchScreen. 

After adding the smoke detector to the 
TouchScreen and installing the smoke detector, 

test the signal strength between the 
TouchScreen and its added sensors/security 

zones: 

A. 

Be sure steps A through D in section 6, 
“Adding to the TouchScreen,” on page 3, 

have been performed. 

Signal Strength Testing 

Annual Testing 

I/M SMCSMXX-Z rev. 2.0 

7/26/11 

Sensitivity Training 

A. 

Press the Test button on the smoke detector 
for 4 seconds. When the test starts, the 

smoke detector LED flashes 1 to 9 times. 

B. 

Count the LED flashes and see the table 
below to determine the status of the smoke 

detector sensitivity and any action to take. 

Understanding the LED 

The smoke detector LED shows the following 
status: 

¾

 

Flash = normal operation 

¾

 

ON = smoke detected, sending an alarm 

¾

 

OFF = trouble or maintenance is required 

Flashes  Meaning 

Steps to Take 

1 Unserviceable 

hardware fault 

Reset smoke detector and 
rerun the sensitivity test. If 

error persists, replace smoke 
detector. 

2 – 3 

Smoke detector 

is becoming 
insensitive 

Clean smoke detector, reset 

it, and rerun the sensitivity 
test. If error persists, replace 
smoke detector. 

4 – 7 

Smoke detector 
is within normal 
sensitivity range. 

None 

8 - 9 

Smoke detector 
is becoming too 
sensitive. 

Verify smoke chamber is 
snapped down securely. 

Clean smoke detector and 
replace the smoke chamber. 

Summary of Contents for SMCSM01-Z

Page 1: ...ed in all common areas and work spaces such as corridors lobbies storage rooms equipment rooms and other tenantless spaces in those environments suitable for proper detector operation in accordance with this code NFPA 72 2 1 4 2 3 Selective Coverage Where codes standards laws or authorities having jurisdiction require the protection of selected areas only the specified areas shall be protected in ...

Page 2: ... to protect and their burning characteristics Human occupancy Total area to be monitored Ceiling height and surface condition Air movement and vent locations Obstructions Deflections After considering these factors choose a location Where the temperature range is between 40 and 100 F 4 4 and 37 8 C Where the humidity is between 0 and 90 noncondensing Away from ventilation sources that can prevent ...

Page 3: ... icon appears for that sensor E Fault each found sensor to pair it to the TouchScreen The icon for each sensor is undarkened as it is faulted and the TouchScreen beeps The sensor is paired to the TouchScreen F When all the sensors are found and paired tap Stop Any located sensors that were not paired are released by the TouchScreen a can be added later The Wireless Sens nd ors M ew its details Cha...

Page 4: ...led D Test communications between the control panel and smoke detector again Press the Test button on the alarm for 8 to 10 seconds The smoke detector sends a signal to the control panel Verify that the signal at the control panel was received E Test the smoke detector see section 9 F The control panel alarm and all auxiliary functions should be verified for a complete test of the system 9 Testing...

Page 5: ... security zones appear tap the zone you want to test for connectivity and follow the instructions from the TouchScreen After adding the smoke detector to the TouchScreen and installing the smoke detector test the signal strength between the TouchScreen and its added sensors security zones A Be sure steps A through D in section 6 Adding to the TouchScreen on page 3 have been performed Signal Streng...

Page 6: ...t or use a soft bristled brush to remove dust and dirt from the smoke chamber base G Line up the new smoke chamber with the optical base by aligning the arrows on the smoke chamber to the latches on the optical base and snap down into place H Replace the detector cap by lining up the cap with the smoke detector Then insert the cap into the smoke detector and turn clockwise approximately 15 degrees...

Page 7: ...B Tap the Turn Zone Off button for the smoke detector The Turn Zone Off button changes to Turn Zone On C When the system is disarmed the Security Status header shows that some zones have been bypassed 12 Delete the Smoke Detector Deleting a sensor such as your SMC Smoke Detector from the premises removes it from being monitored by the customer s system This is not the same as disabling bypassing a...

Page 8: ...ase the tamper switch The LED blinks green F Replace the front cover G Replace all the batteries to the smoke detector and the back cover 14 Compliance Statements Model SMCSM01 Z FCC ID JI5 SMCZB01 IC ID 4137A SMCZB01Z Model SMCSM02 Z FCC ID RU4 HWM6505 ZZ IC ID 9682A HWM6505 ZZ Federal Communication Commission Interference Statement This equipment has been tested and found to comply with the limi...

Page 9: ...areils radio exempts de licence Son fonctionnement est sujet aux deux conditions suivantes 1 le dispositif ne doit pas produire de brouillage préjudiciable et 2 ce dispositif doit accepter tout brouillage reçu y compris un brouillage susceptible de provoquer un fonctionnement indésirable IMPORTANT NOTE Radiation Exposure Statement The product complies with the US Canada portable RF exposure limit ...

Reviews: