background image

 

Copyright 

©

2013 SMC Networks

  

Page 1 

                                                                                                                

All Rights Reserved 

I/M SMCSD10-Z rev. 1.0 

6/18/13 

1   

Product Introduction 

The SMCSD10-Z works with the Touchscreen. The 
device has an optical sensor capable of detecting 
smoke particles in the event of fire. It also has 
an integrated heat sensor that is triggered if a 
room experiences a sharp rise in temperature. 
The SMCSD10-Z does not contain an alarm. 
Audible alerts sound at the Touchscreen.  

The SMCSD10-Z meets FPA 72 field-sensitivity 
testing requirements without the need for 
external meters. Built-in drift compensation 
allows the SMCSD10-Z to adjust sensitivity 
automatically as it becomes dirty over time. The 
drift-compensation feature dramatically 
increases the time between cleanings, as well as 
reducing the chance of a nuisance alarm.  

2   

Parts List 

Your SMCSD10-Z package includes: 

 

(1) SMCSD10-Z Smoke Detector 

 

(2) CR123A lithium batteries  

 

(1) Mounting plate 

 

(1) Mounting screws and anchors 

 

(1) This User Guide 

3   

Tools Required 

 

 Flat-Tipped Screw Driver 

4   

Finding a Suitable Location 

Review this section to ensure you get the most 
out of the 

SMCSD10-Z

. This information is in 

accordance with NFPA 72 depending on country 
of installation. 

Pre-installation Considerations 

Install the SMCSD10-Z in accordance with the 
National Fire Protection Association’s (NFPA) 
Standard 72, Chapters 2 and 8. Depending on the 
application, you may need to reference other 
chapters of NFPA 72 or NFPA 101. 

Choosing an Installation Location 

When choosing an installation location, consider: 

 

Use of structure and type of construction 

 

Contents you want to protect and their 
burning characteristics 

 

Human occupancy 

 

Total area to be monitored 

 

Ceiling height and surface condition 

 

Air movement and vent locations 

 

Obstructions 

 

Deflections 

Recommended Locations 

After considering these factors, choose a 
location: 

 

Where the temperature range is between 40° 
and 100° F (4.4° and 37.8° C). 

 

Where the humidity is between 0 and 90% 
non-condensing. 

 

Away from ventilation sources that can 
prevent smoke from reaching the smoke 
detector. 

 

At least 5 feet (1.5 m) from bathrooms. 

 

 

When placing the SMCSD10-Z on a ceiling, mount 
it in the center of the room or hallway at least 4 
inches (10cm) away from any walls or partitions.  

SMCSD10-Z Smoke Detector Guide 

Congratulations on purchasing your SMCSD10-Z Smoke Detector with Heat Detection Sensor.

 

The SMCSD10-Z Smoke Detector provides triple protection against fire. It combines a photoelectric smoke detector with an integrated heat  
detector that senses both fixed temperature and temperature rate-of-rise within a room. 

 

Summary of Contents for SMCSD10-Z

Page 1: ...Pre installation Considerations Install the SMCSD10 Z in accordance with the National Fire Protection Association s NFPA Standard 72 Chapters 2 and 8 Depending on the application you may need to reference other chapters of NFPA 72 or NFPA 101 Choosing an Installation Location When choosing an installation location consider Use of structure and type of construction Contents you want to protect and ...

Page 2: ...t smoke from reaching a smoke detector Within 10 feet 3 m of fluorescent light fixtures Not suitable for outdoor use WARNING LIMITATIONS OF SMOKE DECTECTORS The SMCSD10 Z Smoke Detector does not contain a built in audio alarm It is not intended for stand alone use it MUST be used with an approved Touchscreen Wireless smoke detectors are very reliable but may not work under all conditions No fire a...

Page 3: ...atteries Do not replace with batteries that were used previously D Reattach the SMCSD10 Z to the mounting base and test the system E The SMCSD10 Z ships with a dust cover for protection on construction sites with dusty environments If your product is new remove the red plastic dust cover from the SMCSD10 Z 6 Pairing with Touchscreen Each SMCSD10 Z is programmed with a unique ID when manufactured T...

Page 4: ...SMCSD10 Z Add the SMCSD10 Z to the Touchscreen before physically mounting it in the desired location A Test communications between the Touchscreen and the SMCSD10 Z as follows before permanently mounting the SMCSD10 Z Hold the SMCSD10 Z where you plan to install it Press the SMCSD10 Z Test button for 10 to 15 seconds The SMCSD10 Z sends a signal to the Touchscreen At the Touchscreen verify the sig...

Page 5: ...e At the Settings Menu touch Security Alarm Tests Follow the Touchscreen s provided directions to place it into Test Mode C To generate a test alarm press and hold Test Button for 15 seconds An alarm message is sent to the Touchscreen The Touchscreen alarm will sound as each sensor is tested D Once completed exit Test Mode from the Touchscreen Using Smoke The SMCSD10 Z can be tested during install...

Page 6: ...ng Zone Event History on this page To bypass a zone A With the system disarmed tap the Security app on the Home screen B Tap the Turn Zone Off button for the smoke detector The Turn Zone Off button changes to Turn Zone On C When the system is disarmed the Security Status header shows that some zones have been bypassed 12 Deleting a Sensor Deleting a sensor from the premises removes it as a monitor...

Page 7: ...F until the SMCSD10 Z is serviced To place the SMCSD10 Z in diagnostic mode A Press the Test Button on the smoke detector for 5 seconds When the test starts the smoke detector LED flashes 1 to 9 times B Count the LED flashes and see the table below to determine the status of the smoke detector sensitivity and any action to take Flash Meaning Steps to Take 1 Unserviceable hardware fault Reset unit ...

Page 8: ... Replace the batteries using the directions in section 5 of this guide 14 Troubleshooting The SMCSD10 Z does not power up properly or reports low battery Be sure the batteries are fully seated within the battery compartment and the polarity is correct Check the battery voltage 3 0 VDC nominal Touchscreen does not respond Follow the instructions in section 9 of this guide to test the SMCSD10 Z link...

Page 9: ... Battery Life 5 years typically USensor Photoelectric Sensitivity 2 2 1 3 ft Drift Compensation Adj 0 5 ft max Heat Detection Fixed 135 F 5 F 57 2 C 2 8 C Heat Rate of Rise 15 F min 105 F 8 3 C min 40 6 C Low Battery Beep 1 every 45 seconds RF Wireless Frequency 2 4 GHz Weight w battery 0 20 lbs 0 09 kg Dimensions 5 6 x 2 4 14 2cm x 6 1cm Storage temperature 4 to 140 F 20 to 60 C Operating environ...

Page 10: ...codes and standards or by the authority having jurisdiction NFPA 72 8 1 4 1 3 2 Detection in New Apartment Buildings Approved single station smoke alarms shall be installed in accordance with 7 6 2 10 of NFPA 101 outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit including basements 101 18 3 4 4 2 For exceptions refer to this section of NFP...

Page 11: ...ediately Don t stop to pack or search for valuables In heavy smoke hold your breath and stay low crawl if necessary The clearest air is usually near the floor If you have to go through a closed door carefully feel the door and door knob to see if undue heat is present If they seem cool brace your foot against the bottom of the door with your hip against the door and one hand against the top edge O...

Reviews: