Installation 

I/M SMCSMXX-Z rev. 2.0 

7/26/11 

Note:

 

Add the SMC Smoke Detector to the 

TouchScreen before physically mounting the 
smoke detector in the desired location. 

A. 

Disconnect alarm-notification appliances, 
service-release devices, and extinguishing 
systems. Test communications between the 

control panel and smoke detector before 
permanently mounting the smoke detector 

as follows: 

Hold the smoke detector where you plan 
to install it. 

Press the smoke detector test button for 

8-to-10 seconds. The smoke detector 

sends a signal to the control panel. 

At the control panel, verify the signal was 

received and RF signal strength is 
adequate. If no signal is received or the 

RF signal is low, relocate the smoke 
detector and retest. 

B. 

Using two supplied screws and anchors, 
mount the base. 

C. 

Attach the smoke detector to the mounting 
base as follows: 

Line up the raised alignment tab on the 

lip of the smoke detector with the arrow 
on the mounting base. 

Insert the smoke detector into the base 
and turn clockwise about 15 degrees until 

it snaps into place. 

Note:

 

The smoke detector cannot be attached 

to the mounting base if no batteries are 

installed. 

 

 

D. 

Test communications between the control 
panel and smoke detector again: 

Press the Test button on the alarm for 8-
to-10 seconds. The smoke detector sends 
a signal to the control panel. 

Verify that the signal at the control panel 
was received. 

E. 

Test the smoke detector (see section 9). 

F. 

The control panel alarm and all auxiliary 

functions should be verified for a complete 
test of the system. 

 

9   

Testing and Maintenance 

¾

 

If a Low battery notification appears on the 

TouchScreen, follow the instructions under 
“Replacing the Battery” on page 6. 

Maintaining the SMC Smoke 
Detector 

The SMC Smoke Detector requires occasional 
maintenance. An alert on the TouchScreen 

indicates when to perform maintenance. The 

Alignment Arrow 

Alignment Tab 

table below shows notification messages the 

TouchScreen may show for a smoke detector. 

If a

 

¾

 

 CleanMe notification appears on the 

TouchScreen, follow the instructions under 

“Cleaning the SMC Smoke Detector” on page 
7. 

¾

 

If a Maintenance alert notification appears 
on the TouchScreen, follow the instructions 

under “Sensitivity Testing” on page 6. 

Signal 

Meaning 

CleanMe 

Smoke detector sensitivity is out of range 
and needs cleaning. 

Maintenance 
alert 

Smoke detector failed power-up self test. 

Perform a sensitivity test (see “Maintaining 
the SMC Smoke Detec” on page 6). If 
problem persists, replace smoke detector. 

Low battery 

Batteries are low and must be replaced as 
soon as possible. 

continued on next page 

Summary of Contents for SMCSM01-Z

Page 1: ...ed in all common areas and work spaces such as corridors lobbies storage rooms equipment rooms and other tenantless spaces in those environments suitable for proper detector operation in accordance with this code NFPA 72 2 1 4 2 3 Selective Coverage Where codes standards laws or authorities having jurisdiction require the protection of selected areas only the specified areas shall be protected in ...

Page 2: ... to protect and their burning characteristics Human occupancy Total area to be monitored Ceiling height and surface condition Air movement and vent locations Obstructions Deflections After considering these factors choose a location Where the temperature range is between 40 and 100 F 4 4 and 37 8 C Where the humidity is between 0 and 90 noncondensing Away from ventilation sources that can prevent ...

Page 3: ... icon appears for that sensor E Fault each found sensor to pair it to the TouchScreen The icon for each sensor is undarkened as it is faulted and the TouchScreen beeps The sensor is paired to the TouchScreen F When all the sensors are found and paired tap Stop Any located sensors that were not paired are released by the TouchScreen a can be added later The Wireless Sens nd ors M ew its details Cha...

Page 4: ...led D Test communications between the control panel and smoke detector again Press the Test button on the alarm for 8 to 10 seconds The smoke detector sends a signal to the control panel Verify that the signal at the control panel was received E Test the smoke detector see section 9 F The control panel alarm and all auxiliary functions should be verified for a complete test of the system 9 Testing...

Page 5: ... security zones appear tap the zone you want to test for connectivity and follow the instructions from the TouchScreen After adding the smoke detector to the TouchScreen and installing the smoke detector test the signal strength between the TouchScreen and its added sensors security zones A Be sure steps A through D in section 6 Adding to the TouchScreen on page 3 have been performed Signal Streng...

Page 6: ...t or use a soft bristled brush to remove dust and dirt from the smoke chamber base G Line up the new smoke chamber with the optical base by aligning the arrows on the smoke chamber to the latches on the optical base and snap down into place H Replace the detector cap by lining up the cap with the smoke detector Then insert the cap into the smoke detector and turn clockwise approximately 15 degrees...

Page 7: ...B Tap the Turn Zone Off button for the smoke detector The Turn Zone Off button changes to Turn Zone On C When the system is disarmed the Security Status header shows that some zones have been bypassed 12 Delete the Smoke Detector Deleting a sensor such as your SMC Smoke Detector from the premises removes it from being monitored by the customer s system This is not the same as disabling bypassing a...

Page 8: ...ase the tamper switch The LED blinks green F Replace the front cover G Replace all the batteries to the smoke detector and the back cover 14 Compliance Statements Model SMCSM01 Z FCC ID JI5 SMCZB01 IC ID 4137A SMCZB01Z Model SMCSM02 Z FCC ID RU4 HWM6505 ZZ IC ID 9682A HWM6505 ZZ Federal Communication Commission Interference Statement This equipment has been tested and found to comply with the limi...

Page 9: ...areils radio exempts de licence Son fonctionnement est sujet aux deux conditions suivantes 1 le dispositif ne doit pas produire de brouillage préjudiciable et 2 ce dispositif doit accepter tout brouillage reçu y compris un brouillage susceptible de provoquer un fonctionnement indésirable IMPORTANT NOTE Radiation Exposure Statement The product complies with the US Canada portable RF exposure limit ...

Reviews: