Chapter 4 Starting the Product
4.1 Before Starting
Check the following items before starting the product.
Installation conditions
z
Check the product is installed horizontally.
z
Check that there are no heavy objects on the product, and the external
piping is not applying excessive force to the product.
Connection of cables
z
Check the power, ground and communications (optional) cables are
correctly connected.
Circulating fluid
z
Check proper connection of piping at inlet and outlet.
Facility water piping
(For water-cooled type)
z
Check proper connection of piping at the facility water inlet and outlet.
z
Check that the facility water source is in operation.
z
Check that the facility water circuit is not shut off by valves
[Tips]
The product is equipped with a water regulator, which does not allow the
facility water to flow unless the product is started.
Automatic fluid filling piping (When option
J [With automatic fluid filling] is
selected
z
Confirm that the automatic fluid filling port piping is connected properly.
Over flow port piping (When option
J [With automatic filling] is selected).
z
This is necessary when automatic fluid filling function is used.
Fluid level indicator (for tank)
z
Ensure that the fluid level is on “H”.
Only people who have sufficient knowledge and experience about the
product and its accessories are allowed to start and stop the product.
The facility water should be checked for whether or not it satisfies the
water quality standard described in “8.1 Control of Circulating Fluid
Quality” and requirements specified in “9.1 Specifications List”.