HRX-OM-M090
Chapter 3 Transport and Setting Up
HRS Series
3.4
Piping
3-17
3.4 Piping
Piping port size
Table 3-5 Piping port size
Name
Port size*
1
Recommended
tightening torque
Recommended proof
pressure for piping
Circulating fluid supply
Rc1/2
28 to 30N
・
m
0.4MPa more
Circulating fluid return
Rc1/2
28 to 30N
・
m
0.4MPa more
Faiclity water inlet*
2
Rc3/8 22 to 24N
・
m
Faiclity water outlet*
2
Rc3/8
22 to 24N
・
m
1.0MPa more
(Facility water pressure 0.3 to
0.5 MPa)
Automatic water-fill port *
3
Rc3/8
22 to 24N
・
m
1.0MPa more
(Automatic water-fill pressure
0.2 to 0.5MPa)
Overflow port
*
3
Rc3/4
28 to 30N
・
m
Inside diameter 19mm more of
piping
∗
1
For NPT and G thread, use a conversion connector available as an accessory separately.
∗
2
For water-cooled type.
∗
3
For automatic fluid filling [Option]
z
Connect piping firmly. Incorrect piping might cause leakage of
supplied or drained leakage and wet surrounding area and facility.
z
Keep supply water pressure below 0.5MPa.
z
Pay attention not to allow dust and foreign materials to enter into
water circuit etc. during connection of piping.
z
When the thermo-chiller is water-cooled refrigerated type, the
temperature of the outlet of the facility water may become approx.
60
o
C depending on operating conditions
z
Hold the piping port firmly with specific wrench when tightening.
z
The piping should be selected with due consideraton of pressure and
temperature. Otherwise, the piping can burst in service.
z
Do not use the materials that rust or corrode for the circulating fluid
and facility water circuits. Using the materials that tend to rust or
corrode may cause clogs or/and leakages of the circulating fluid and
facility water circuits. In case of using these kind of materials,
consider and carry out some prevention against the rusting or
corrosion by the customer side.
z
Do not generate a rapid change of pressure by water hammer etc.
The product and external piping might be damaged.
z
Check the model number of this product in "1.4.1 Product Label” of
this manual before connecting piping.
z
Model number: HRS0
∗∗
-
∗
N-
∗
0
The transition connector from Rc to NPT is enclosed as an accessory.
For NPT piping, be sure to use this connector.
z
Model number: HRS0
∗∗
-
∗
F-
∗
0
The transition connector from Rc to G is enclosed as an accessory.
For G piping, be sure to use this connector.