Chapter 5 Display and setting of various functions
HRS Series
5.8
Signal for completion of preparation (TEMP READY)
5-21
5.
Select READY band width (upper/lower temperature range) from the table below with
[
▲
] key or [
▼
] key, and confirm by pressing “SEL”.
Table 5.8-3
List of set value
Set value
Explanation
Initial
(Default setting)
Setting and checking are not available when
READY mode setting is OFF.
Centigrade
to
Fahrenheit
to
Set READY band width (upper/lower
temperature range) for the circulating fluid
temperature
Temperature unit is Centigrade : Setting unit is
0.1
o
C
Temperature unit is Fahrenheit : Setting unit is
0.1
o
F
READY time Set and checking
6.
Press the [SEL] key once.
The set screen of READY time is displayed on the digital display.
PV
SV
7.
Select READY time from the table below with [
▲
] key or [
▼
] key, and confirm by
pressing “SEL”.
Table 5.8-4
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are not available when
READY mode setting is OFF.
to
Sets ultimate time.
Set unit is 1 sec.
8.
Press the [MENU] key once.
Return to the main screen (screen displaying the circulating fluid temperature).
PV
SV