Table 7-2 Alarm code list and Troubleshooting (2/2)
Code
Descriptioin
Operation
Cause / Remedy
(Press the reset key after eliminating the cause.)
AL31
∗
4
Contact input1 signal
detection
∗
4
AL32
∗4
Contact input 2 signal
detection
∗4
Stop
∗
1
Contact input is detected.
AL33
Water leakage
Stop
∗
1
・
Check if the leakage sensor is connected.
・
Leakage occurred. Check the leakage point.
AL34
Electric
resistivity/conductivity rise
Continued
Electric resistivity/conductivity is larger than the set value.
If an electric conductivity sensor is used, replace the DI
filter.
AL35
Electric
resistivity/conductivity drop
Continued
Electric resistivity/conductivity is smaller than the set value.
If an electric resistivity sensor is used, replace the DI filter.
AL36
Electric
resistivity/conductivity
sensor error
Continued
・
Check if the resistivity/conductivity sensor is connected.
・
There may be short circuit or open wire of the resistivity
/conductivity sensor. Replace the sensor.
∗
1
:
’’Stop” or “Continued” are default settings. The user can change them to “Continued” and “Stop”. For details, refer
to ’’5.16 Alarm customize function’’.
∗
2:”AL19, Communication error” is disabled in the default setting. When this function needs to be enabled, refer
to ’’5.19 Communication function’’.
∗
3: For air-cooled type.
∗
4
:
The functions of “AL31 Contact input 1 Signal detection” and “AL32 Contact input 2 Signal detection” are not
default settings. If these functions are used, refer to “5.19Communication function”.
7.4 Other Errors
How to check other errors
The causes and remedies for failures that are not indicated by alarm
numbers are shown in ’’Table 7-3
’’.
Table 7-3 Causes and remedies for failures without alarm number
Content of failure
Cause
Remedy
The power supply switch is not
turned on.
Turn on the power supply switch.
Failure of power supply switch
Replace the power supply switch.
No power supply
(The breaker for the power supply
is not turned on.)
Supply the power.
The operation panel
displays nothing
Trip of breaker due to short-circuit
and current leakage
Repair the short-circuit or current
leaking part.
Communication is set.
Check the presence of communication
setting.
Failure of the [RUN] LED
Replace the controller.
The [RUN] LED does
not light up even when
the [RUN/STOP] switch
is pressed.
Failure of the [RUN/STOP] switch
Replace the controller.