HRX-OM-M090
Chapter 3 Transport and Setting Up
3.3
Installation
HRS Series
3-14
3.3.5
Wiring of operation signal output and alarm signal output
The operation signal output and alarm signal output are the outputs
generated by a contact signal to shown the status of the product.
The specifications of the contact for each signal output are as follows.
Table
3-4
Signal output contact spec. at the time of shipment
Contact output
Signal explanation
(Default setting)
Operation
At run
:
Contact closed
At stop
:
Contact open
Output current 1
(Terminal no.5,6)
Run status signal
A
With power supply
shut off
:
Contact open
At remote
:
Contact closed
At non remote
:
Contact open
Output current 2
(Terminal no.3,4)
Remote signal
A
With power supply
shut off
:
Contact open
At generation
:
Contact open
Not generated
:
Contact closed
Output current 3
(Terminal no.1,2)
Alarm signal
B
With power supply
shut off
:
Contact open
【
Tips
】
This product has three output signals which can be customized depending on
the customer’s application
Signals below can be output. Refer to the Communications Operation Manual
for more details.
・
Signal for completion of preparation (TEMP READY)
・
Signal for operation stop alarm
・
Signal for continuing operation alarm
・
Signal for selection alarm
・
Signal for operation start timer setting
・
Signal for operation stop timer setting
・
Signal for power recovery setting
・
Signal for freezing prevention setting
・
Contact input signal detection
Be sure to shut off the breaker of the facility power supply (the user’s
machine power supply) before wiring.